In DeltaV Explorer, navigate to the Modbus ports of an LSNG. Select Modbus Port 1 and from the context menu, select Device. The Properties dialog for the device on the selected port opens. Configure both the General and Advanced tabs for both devices.
This IP address should be the same as that configured in the AS tool.
A value of 0 (zero) indicates that the device is ready for a command and a value of 1 (one) indicates that it is not ready.
These are Boolean with status parameters and count against the number of Booleans that are published by the LSNG. If these parameters are configured for both ports then only 766 signals can be published.
Now configure the device on Modbus Port 2.
Because the two devices are paired, only a few fields on the Modbus Port 2 device are configurable. Many of the fields in the second device (Port 2) must match exactly with the fields in the first device (Port 1) because the LSNG is comparing the data received between them. The Device Command data will be unique because the devices can be commanded separately (if necessary). Note that with interconnected devices, this is not always necessary.