CHARMs Smart Logic Solver configuration

SIS Controller configuration

DeltaV SIS Controllers appear in DeltaV Explorer under the Control Network.

Figure: DeltaV SIS Controller (SISCTLR1) in DeltaV Explorer


With the exception that SIS Controllers do not support local I/O, SIS Controllers have the same properties as other DeltaV controllers, including redundancy.

The Assigned Modules subsystem supports the same options as the DeltaV Controller except the only module type that can be added is a control module or template. Class-based and classless unit and equipment modules as well as phase logic modules are not supported. The Assigned I/O subsystem holds the remote I/O assignments from CIOCs and Zone1/Zone2 Remote I/O. The Assigned Wireless I/O subsystem holds the I/O assignments from WIOCs and wireless gateways.