CHARMs Smart Logic Solver configuration

Secure parameters in CSLS

Each CSLS can contain as many as 96 Boolean and 32 non-Boolean secure parameters. Secure parameters are configured in SIS modules.

A SIS module can contain as many as 96 Boolean and 32 non-Boolean secure parameters.

CSLS secure parameters can be referenced by any module in any CSLS. Modules on other LSNs can access secure parameters through the LSNB and the GSN.

Secure parameters are maintained by publishers. These are software entities within the database, hosted on LSNBs. When a secure parameter is referenced by some node, the relevant publisher creates a secure parameter mapping that shows the parameter data and the referencing system.