This section outlines how to bulk edit DeltaV SIS Controller Modbus
port registers mappings to module. There are a few conditions that must be met
to bulk edit register mapping:
- Each register_type value
must be correct for the corresponding register_name. For example,
register_names between R10001 and R11000 must be register_type
Input status.
- Importing more register
mappings than the allowed number of registers for a particular type imports
only the registers up to the maximum allowed value.
- The register_name for
Float input and Float holding register types must end with an odd number.
- If the bulk edit file
contains gaps in the register_name list (for example R1 and R3 exist in the
file but R2 does not), the omitted registers are created on import but are not
mapped.
Note
Bulk edit can add or modify registers but cannot remove registers.
The only way to remove registers is from the
Modbus Port Properties dialog
Data sets tab.
The general procedure to bulk edit is: