| Name | Context | Path | Description |
|---|---|---|---|
|
DeviceStatus |
CSLS |
CSLS_NAME/DEVICE_STATUS, CSLS_NAME/REDU/STBY/DEVICE_STATUS |
Status of the CSLS and removable components |
| Conditions | Meaning | Mapping | Impacts Integrity |
|---|---|---|---|
| Primary 24 Volt Power Invalid | The primary 24V power supply is not connected or is out of range | Maintenance | Y |
| Secondary 24 Volt Power Invalid | The secondary 24V power supply is not connected or is out of range | Maintenance | Y |
| Left Power Module Not Installed | The left Power Module is not installed | Maintenance | Y |
| Right Power Module Not Installed | The right Power Module is not installed | Maintenance | Y |
| Left Power Module Failed | An error has been detected in the left Power Module | Maintenance | Y |
| Right Power Module Failed | An error has been detected in the right Power Module | Maintenance | Y |
| Left SNP Error | The left SISNet Port has failed or is not installed. | Maintenance | Y |
| Right SNP Error | The right SISNet Port has failed or is not installed. | Maintenance | Y |
| Left Non-Volatile Memory Error | An error has occurred in the NVM in the left SISNet Port | Maintenance | Y |
| Right Non-Volatile Memory Error | An error has occurred in the NVM in the right SISNet Port | Maintenance | Y |
| CHARMs Logic Solver Lost Time Sync | The CSLS has lost time sync with the SZ Controller | Maintenance | Y |