| Name | Context | Path | Description |
|---|---|---|---|
|
DiagStatus |
CSLS |
CSLS_NAME/DIAG_STATUS, CSLS_NAME/REDU/STBY/DIAG_STATUS |
Status of the Diagnostic Subsystem |
| Conditions | Meaning | Mapping | Impacts Integrity |
|---|---|---|---|
| Past Error Present | A condition is present in the CSLS PAST_ERROR parameter. | --- | N |
| Persistent Fatal Error After Powerup | The same PAST_ERROR condition was present on back-to-back resets. The CSLS is not fully operational. | Maintenance | Y |
| Task Checkpoint Alarm | A non-critical task has not completed properly in one of the subsystems in the CSLS. | Advise | Y |
| Non-Volatile Memory Failure | An NVM chip failure has been detected | Maintenance | Y |
| Real Time Clock Failure | An RTC chip failure has been detected | Maintenance | Y |
| Internal A/D Error | An A/D chip failure has been detected | Maintenance | Y |
| Internal Power Error | The CSLS has detected an internal power supply voltage out of range. | Maintenance | Y |