Automatic proof testing is available for redundant CSLSs only. The
Proof Testing tab of the
CSLS Properties dialog has an
Enable automatic proof test to run at reminder
time check box. When checked, the CSLS performs the proof test when
the number of days since the last reset reaches the configured time. The
automatic proof test will begin after the CSLS sets the reminder alert. At the
time of automatic proof test:
- The Active card starts the
test by initiating a switchover to the Standby card. If the Standby card is not
available, the Active card tries again periodically.
- After switchover the
Standby card becomes Active and the new Standby card goes through reset and
begins power-up testing. There is no adverse impact to the running process. An
event record confirms successful power-up testing.
- The new Active card may
still have a proof test due, and if so, it waits for its partner to become
available then initiates a switchover. When the partner has become the Active
card, the new Standby card goes through reset and power-up testing. An event
record confirms successful power-up testing of the CSLS card.