Manually proof test redundant CHARMs Smart Logic Solvers
(CSLS)
The procedure for a redundant CSLS allows the proof test to be done
online without adversely affecting the running process.
The logic solver can be manually reset only when the CSLS is
Unlocked. Select the CSLS in Diagnostics Explorer. If the value of the Locked
parameter is
Yes in the contents pane, right-click on the
CSLS and select
Unlock. Click
Confirm on the
Secure Write Confirmation dialog.
Right-click the CSLS and select
Force Reset on Standby. Click
Confirm on the confirmation dialog.
Wait for the Standby card to complete power-up tests and become
configured by the Active card. The
Partner Not Available maintenance alert goes
inactive when the Standby card is fully configured.
Right-click the CSLS and select
Switchover. Click
Confirm on the confirmation dialog.
The previously reset Standby card becomes the new Active card and
the new Standby card goes through power-up tests and is configured by the new
Active card. The proof test timer is 0. There will be event records for the
user reset and switchover commands and for the CSLS cards, confirming that
power-up tests completed successfully.