If Preserve Network Definition is selected, the network configuration, including workstations, controllers, I/O cards, and logic solvers is copied to the new database. Module assignments and area and recipe assignments are also copied. Modules (except assigned SIS modules) are not copied.
If Preserve Network Definition is not selected, an empty database is created and you must run workstation configuration to define the ProfessionalPLUS workstation and then configure other items in your network.