FFPid_dt (Fieldbus PID function block detail display)

Configuration view of the Fieldbus PID detail display (FFPid_dt)

The FFPid_dt is used with the PID function block used with a Fieldbus PID Loop module. The following sections describe the major components that are present on the FFPid_dt.

Alarm icon
Shows the highest priority alarm for that module. The following table shows the alarm icon for each alarm priority and state.
Active acknowledged Active unacknowledged Inactive unacknowledged Suppressed
Critical alarm
Warning alarm
Advisory alarm
Note:
The suppressed alarm icon is visible only when no other active or unacknowledged alarms exist.
Faceplate button
Opens the module faceplate display.
Limits
Hi Hi Lim
The maximum value of the PV (in engineering units) before the High High Limit active bit (HI_HI_ACT) is set. Click this field to enter a new limit.
Hi Lim
The maximum value of the PV (in engineering units) before the High Limit active bit (HI_ACT) is set. Click this field to enter a new limit.
Dev Hi Lim
The maximum positive deviation of the PV from SP (in engineering units) before the High Deviation Limit active bit (DV_HI_ACT) is set. Click this field to enter a new limit.
Dev Lo Lim
The maximum negative deviation of the PV from SP (in engineering units) before the Low Deviation Limit active bit (DV_LO_ACT) is set. Click this field to enter a new limit.
Lo Lim
The minimum value of the PV (in engineering units) before the Low Limit active bit (LO_ACT) is set. Click this field to enter a new limit.
Lo Lo Lim
The minimum value of the PV (in engineering units) before the Low Limit active bit (LO_ACT) is set. Click this field to enter a new limit.
Out Hi Lim
The maximum value, in engineering units, of the output. Click this field to enter a new limit. (The valid input range for this value is -10 to 110 % of the output scale, in engineering units.)
Out Lo Lim
The minimum value, in engineering units, of the output. Click this field to enter a new limit. (The valid input range for this value is -10 to 110 % of the output scale, in engineering units.)
SP Hi Lim
The maximum value of the SP, in engineering units. Click this field to enter a new limit. (The valid input range for this value is -10 to 110 % of the PV Scale, in engineering units.)
SP Lo Lim
The minimum value of the SP, in engineering units. Click this field to enter a new limit. (The valid input range for this value is -10 to 110 % of the PV Scale, in engineering units.)
Alm Hysteresis
The alarm hysteresis (or deadband) value for the alarm conditions in % of OUT scale. Click this field to enter a new value. An alarm condition does not recur until the PV has backed away from the corresponding limit by at least the % of OUT Scale specified by this value.
Tuning
Gain
The gain used in the PID algorithm.
Reset
The integral time constant used in the PID algorithm.
Rate
The derivative time constant used in the PID algorithm.
PV Filter TC
The PV filter time constant in seconds.
SP Filter TC
The PV filter time constant in seconds.
SP Rate DN
In engineering units, the maximum negative change to the WORKING_SP that are allowed per second (SP_RATE_DN). Click this field to enter a new value. A value of 0.0 indicates that no rate limiting will be done.
SP Rate UP
In engineering units, the maximum positive change to the WORKING_SP that are allowed per second (SP_RATE_UP). Click this field to enter a new value. A value of 0.0 indicates that no rate limiting will be done.
IDeadband
The integral deadband. When the error (WORKING_SP minus PV) is less than this value, integral action stops.
When the Structure is PD or P–D, Bias replaces this value.
FF Gain
The feedforward gain (FF_GAIN). This field is visible when FF_ENABLE is True.
Beta
The fraction of proportional action taken on error versus PV. The valid input range is 0.00 to 1.00. This field is visible when STRUCTURE is set to Two Degrees of Freedom Controller.
Gamma
The fraction of derivative action taken on error versus PV. The valid input range is 0.00 to 1.00. This field is visible when STRUCTURE is set to Two Degrees of Freedom Controller.
Adaptive Mode
The Actual and Target modes. Click the drop–down arrow to change the Target mode.
DeltaV Insight button
Launches DeltaV InSight in the context of this module.