Controller LEDs

Table: SD Plus, SX, and SQ controller LEDs
LED correct operating condition Fault indication Possible causes and corrective action
Power-On (green) Off System power is not supplied to the controller due to a possible line power problem. Check the power connections.
Internal fault. Contact technical support.
Error-Off Red (continuous) Internal fault. Contact technical support.
Red-On for one second followed by all LEDs on for five seconds. Controller went through a reset due to an unrecoverable software error. Contact technical support.
Red (flashing) The controller is decommissioned. Commission the controller.
Active-On (green) Off Controller is a standby. Ensure that the Standby LED is On.
Controller is decommissioned. Commission the controller.
Internal fault. Contact technical support.
Green (flashing) Controller is not configured. Download the controller configuration.

Standby-On (green) for redundant controllers

Off for simplex controllers

Green (flashing) Controller is not configured. Download the controller configuration.
Pri. CN – Yellow (flashing) Off Controller lacks active Ethernet communications on the primary control network connection. Check the cable and switch connections on the primary control network
Sec. CN – Yellow (flashing) Off Controller lacks active Ethernet communications on the secondary control network connection. Check the cable and switch connections on the secondary control network.