General information about function blocks > Function block modes

Mode shedding logic

Shed from or climb to a remote mode is determined by the parameter SHED_OPT. A block climbs and sheds through the same path. For example, if SHED_OPT specifies that a block should shed to Auto, then, if the block target mode is set to RCas, the block goes through Auto on the way to RCas.

Note

Consider the effect of the fault state when selecting the mode shed option. Keep in mind that the fault state can cause the mode to go to Local Override instead of the expected mode from mode shedding.

Configuring shed

The parameter SHED_OPT determines shed and climb for a remote mode. It can be configured as follows:

Shed With Return Options

Remote cascade connection failure shifts actual mode but keeps trying to restore remote cascade (in other words, the remote cascade target mode stays in effect).

Shed With No Return Options

For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no attempt to restore the connection following failure. The behavior on change to the remote cascade target mode is identical to that for Shed With Return Options.

It is possible for the user to configure SHED_OPT so that it calls for a target mode that is not permitted. When doing this, the mode logic does the following rules as applied by the remote logic: