|
AV_HI_LIMIT[1…80]
|
The constraint high limit.
|
|
AV_LO_LIMIT[1…80]
|
The constraint low limit.
|
|
FAIL_ACTION_OUT[1…80]
|
- 0=No Action
- 2=Shed downstream
modes
- 3=Manual
- 4=Simulate Manual
- 5=Simulate Shed
downstream modes
|
|
FAIL_ACTION_IN[1…40]
|
- 0=No Action
- 1=Hold last good
value (applies to DVs only)
- 2=Shed downstream
modes
- 3=Manual
|
|
INPUT_DISABLED[1…40]
|
The
Disable button on the DV faceplate:
- 0=Not disabled
- 1=Disabled
|
|
MASTER_SWITCH
|
The MPC/LOCAL switch of the block:
- 0=Local control
- 1=MPC control
When written to, switches all downstream blocks
simultaneously. Every write to this parameter is a write to the target mode of
all downstream blocks. Note: Do not write every scan; doing so would prevent
the operator from changing the downstream blocks' target mode.
|
|
MASTER_SWITCH_MV[1…40]
|
The MPC/LOCAL switch for each MV.
|
|
MV_HI_LIMIT[1…40]
|
The maximum output value (in engineering units) that an
operator can enter. An entry that is greater than this limit is truncated to
the limit value.
|
|
MV_LO_LIMIT[1…40]
|
The minimum output value (in engineering units) that an
operator can enter. An entry that is lower than this limit is truncated to the
limit value.
|
|
MV_MAX_RATE[1…40]
|
The maximum rate (in engineering units per second) at which
the MPCPro function block can change the Manipulated parameter.
|
|
OPT_COST_IN[1…40] [1…5]
|
The MV cost value for optimization. [1-5] indicates the
Objective Function.
|
|
OPT_PROFIT_OUT[1…80] [1…5]
|
The output cost value for optimization. [1-5] indicates the
Objective Function.
|
|
OPT_PSV[1…40]
|
The Preferred Settling Value. This value usually represents a
valve position to which the Manipulated variable is driven if PSV is selected
under Optimization and there are extra degrees of freedom after all
minimize/maximize optimization targets have been achieved.
|
|
OPT_TYPE_IN[1…5] [1…40]
|
The optimization type for MVs:
- 0=None
- 1=Maximize
- 2=Minimize
- 4=PSV
- 5=Equalize
[1-5] indicates the Objective Function.
|
|
OPT_TYPE_OUT[1…5] [1…80]
|
The optimization type for process outputs:
- 0=None
- 1=Maximize
- 2=Minimize
- 3=Target
- 4=PSV
[1-5] indicates the Objective Function.
|
|
OPT_OBJ_INDEX
|
The currently selected Objective Function (values are 1-5).
|
|
OUTPUT_DISABLED[1…80]
|
The Disable button the CV and AV faceplates:
- 0=Not disabled
- 1=Disabled
|
|
PREDICTION[1…80][1…10]
|
For each process output, an approximated trajectory is
communicated by the block. (Approximated is defined as ten points (of 120)
where 10 is the last point in the future prediction.) For example:
- Read
PREDICTION[3][10] to observe the last point of the prediction of PROC_OUT[3].
- Read
PREDICTION[1][5] to observe a point approximately half way into the prediction
horizon of PROC_OUT1.
|
|
ROTATION_LIMIT[1…80]
|
The maximum accepted value of the rotation factor.
|
|
SIM_COUNTDOWN[1…80]
|
Shows how long (in seconds) a particular process output is
simulated before Manual mode or Shed of downstream blocks occurs. Read-only.
|
|
SP_HI_LIMIT[1…80]
|
The setpoint high limit. A setpoint entry that is higher than
this limit is truncated to the limit value.
|
|
SP_LO_LIMIT[1…80]
|
The setpoint low limit. A setpoint entry that is lower than
this limit is truncated to the limit value.
|
|
SP_DELTA_RANGE[1…80]
|
The setpoint range that is the maximum amount that the
optimizer can change the setpoint used in control from the operator-specified
setpoint.
|
|
SP_FTIME[1…80]
|
The Response Trajectory is an exponential trajectory defined
by its filter time constant, current process output, and future required
process output (SP). Response Trajectory is used to increase stability by
slowing down the controller reaction to CV error. When unmeasured disturbances
are significant, Response Trajectory filter time constant values between 1 and
5 times the TSS are recommended.
|
|
SP_HI_RANGE[1…80]
|
A read-only parameter that presents the high limit that is
actually used by the optimizer.
|
|
SP_LO_RANGE[1…80]
|
A read-only parameter that presents the low limit that is
actually used by the optimizer.
|
|
SP_TRACKING[1…80]
|
When enabled, the SP tracks the Controlled parameter value
when the MPCPro block is in a Target mode of MAN or an Actual mode of IMAN.
- 0=SP tracking
disabled
- 1=SP tracking
enabled
|