A_NUM_TO_TRIP
(8-bit unsigned integer)
|
0
|
The actual number of votes needed to trip. This can differ
from NUM_TO_TRIP if there are bypassed inputs and the BYPASS_OPTS option,
A maintenance bypass reduces the number to
trip, is selected.
|
|
BYPASSn
(Boolean)
|
False
|
If BYPASSn is True, IN_Dn is excluded from
voting to trip.
|
|
BYPASS_OPTS
(Option bitstring)
|
None
|
Configurable options for maintenance and startup bypass
behavior. Options are kept in a bitstring internally. The options are:
-
A maintenance bypass reduces the number to trip
-
Multiple maintenance bypasses are allowed
-
Maintenance bypass timeout is for indication only
-
Startup bypass preset is allowed while active
-
Startup bypass expires upon stabilization
-
Reminder applies to startup bypass
-
Startup bypass duration is event based.
-
Bypass permit is not required to bypass
-
Bypass permit control should be visible in operator
interface
|
|
BYPASS_PERMIT
(Boolean)
|
False
|
Must be True for any BYPASSn parameter to be True when
the BYPASS_OPTS option,
Bypass permit is not required to bypass,
is not selected. When this option is selected, the block ignores BYPASS_PERMIT.
|
|
BYPASS_TIMEOUT
(Floating point)
|
0
(Seconds)
|
The number of seconds any BYPASSn can be True before
the block sets all BYPASSn parameters to False unless the BYPASS_OPTS
option,
Maintenance bypass timeout is for indication
only, is selected. If that is true or if the value of
BYPASS_TIMEOUT is 0.0, the block will not remove bypasses.
|
|
BYPASS_TIMER
(Floating point)
|
0
(Seconds)
|
Countdown timer for the bypass function in seconds.
|
|
BYPASS_TIMER_H
(Floating point)
|
0
(Hours)
|
Countdown timer for the bypass function in hours.
|
|
DELAY_TIMER
(Floating point)
|
0
(Seconds)
|
Countdown timer for the TRIP_DELAY and NORMAL_DELAY parameters
to determine if the output is tripped or normal.
|
|
DESCn
(String)
|
None
|
Configurable label for IN_Dn
|
|
DVTR_ALERTS
(Option bitstring)
|
None
|
Parameter containing the runtime value of alarm conditions set
by the block (inactive = 0, active = 1)
-
Trip Active
-
Bypass Active
-
Startup Override Active
-
Expiration Reminder
-
Bypassed Input Tripped
-
Input Bad
|
|
IN_Dn
(Discrete with status)
|
0
|
Discrete value from a single sensor. IN_Dn is
extensible from 1 to 16. The default input count is 3.
|
|
NORMAL_DELAY
(Floating point)
|
0
(Seconds)
|
The number of consecutive seconds before OUT_D changes to the
normal operation value after the number of votes to trip falls below the number
required to trip.
|
|
NUM_TO_TRIP
(8-bit unsigned integer)
|
2
|
The configured number of votes needed to initiate a trip
condition
|
|
OUT_D
(Discrete with status)
|
0
|
The output of the block, either Normal (1) or Tripped (0) as
determined by the trip vote function.
|
|
OUT_D_NOBYPASS
(8-bit unsigned integer)
|
0
|
The value OUT_D would have if all BYPASSn parameters
were False and a startup bypass is not active.
|
|
REMINDER_TIME
(Floating point)
|
0
(Seconds)
|
The amount of time an alarm is active prior to the timeout of
a maintenance or startup bypass timer if a trip is imminent.
|
|
REPORT_OPTS
(Option bitstring)
|
None
|
Configurable options for block reporting features.
-
Alarm conditions do not roll up to module level.
This option applies only to block alarms and events and not
user-defined module alarms.
|
|
STABLE_TIME
(Floating point)
|
0
(Seconds)
|
The time configured to allow for process stabilization during
a startup bypass. This is the number of consecutive seconds without a vote to
trip while the startup bypass is active. Optionally, the startup bypass expires
when the actual stabilization time reaches the configured allowed time.
|
|
STABLE_TIMER
(Floating point)
|
0
(Seconds)
|
The actual number of consecutive seconds without a vote to
trip while the startup bypass is active.
|
|
STARTUP
(Boolean)
|
False
|
Inhibits trip detection during startups. On a rising edge of
STARTUP, the block keeps OUT_D in the normal operating state for STARTUP_TIME
seconds when the BYPASS_OPTS option,
Startup bypass duration is event based,
is False.
When the BYPASS_OPTS option,
Startup bypass duration is event based,
is selected, a startup bypass is active when STARTUP is True and inactive when
STARTUP is False).
|
|
STARTUP_TIME
(Floating point)
|
0
(Seconds)
|
The number of seconds the startup inhibit function is in
effect following a rising edge of STARTUP.
|
|
STARTUP_TIMER
(Floating point)
|
0
(Seconds)
|
Countdown timer for the startup inhibit function.
|
|
STATUS_OPT
(Option bitstring)
|
Always use Value
|
Determines the behavior when the status of any IN_Dn
input is Bad. Choices are:
-
Always Use Value
-
Will Not Vote if Bad
-
Vote to Trip if Bad.
|
|
TIME_TO_STABLE
(Floating point)
|
0
(Seconds)
|
The total number of seconds during a startup bypass until the
inputs became and remained stable.
|
|
TRIP_DELAY
(Floating point)
|
0
(Seconds)
|
The number of consecutive seconds with enough votes to trip
before OUT_D changes to the trip state value.
|
|
TRIP_STATUS
(Named Set)
|
Normal
|
Indicates the status of the trip vote and startup inhibit
functions:
-
Normal
-
Tripped
-
Trip Inhibited
-
Voted to Trip - Delayed
-
Voted Normal - Delayed
|
|
TRIP_VOTE_INn
(Boolean)
|
False
|
A True value indicates IN_Dn is voting to trip.
|
|
TRIP_VOTES
(8-bit unsigned integer)
|
0
|
The number of inputs that have voted to trip. Bypassed inputs
are not included in the total.
|