The following table lists the system parameters for the Filter function block.
Parameter |
Units |
Description |
|---|---|---|
FOLLOW |
None |
Selects whether to filter the input (0) or track the input (1). When FOLLOW is True (1), the filter algorithm does not execute and OUT tracks IN. |
IN |
Determined by source |
The analog input value and status. |
OUT |
Determined by IN |
The analog output value and status. |
TIMECONST |
Seconds |
The time constant. Specifies the time for OUT to equal 63% of IN. |
Default values and data type information for the parameters are available by expanding the Parameter View window.