The following table lists the system parameters for the H1 Carrier Multiple Discrete Output function block:
Parameter |
Units |
Description |
|---|---|---|
ABNORM_ACTIVE |
None |
The indication that a block error condition not selected in BAD_MASK is True (Active). |
ALERT_KEY |
None |
A user-assigned identification number reported in alarm messages from the block that allows HMI applications to sort and filter alarms and events. Set this parameter for each function block to indicate the physical unit the function block is associated with. This information can be used in the host for sorting alarms, and so on. |
BAD_ACTIVE |
None |
The indication that a block error condition selected in BAD_MASK is True (Active). |
BAD_MASK |
None |
The set of active error conditions that triggers a user-defined Bad condition. The user selects a subset of block error (BLOCK_ERR) conditions in the BAD_MASK parameter. When any of these conditions are True, the BAD_ACTIVE parameter becomes True. When any of the BLOCK_ERR conditions that are not included in BAD_MASK are True, ABNORM_ACTIVE becomes True. |
BKCAL_OUT_D |
None |
The value and status required by the BKCAL_IN_D input of another block. |
BLOCK_ERR |
None |
|
CAS_IN_D |
None |
The remote setpoint value from another block. |
CHANNEL |
None |
The number of the logical hardware channel that is connected to the I/O block. It defines the transducer to be used going to or from the physical world. |
FSTATE_TIME |
Seconds |
The time in seconds from detection of fault of the output block remote setpoint to the output action of the block output if the condition still exists. |
FSTATE_VAL_D |
EU of PV |
The preset discrete SP_D value to use when fault occurs. Ignored if the I/O option Fault State to value is false. |
IO_OPTS |
None |
|
MODE |
None |
The mode record of the block. Contains the actual, target, permitted, and normal modes. |
OUT_D |
None |
The 8-bit integer output value and status. |
PV_D |
None |
The 8-bit integer process variable calculated from READBACK_D. |
RCAS_IN_D |
None |
The remote setpoint value and status. Input provided by a device or the output of another block. |
RCAS_OUT_D |
None |
The remote setpoint value and status output provided to a device to allow action to be taken under mode change. |
READBACK_D |
None |
The value and status of OUT_D unless simulation is enabled, in which case it is the simulated value and status. |
SHED_OPT |
None |
Defines action to be taken on remote control device time out. |
SIMULATE_D |
None |
Enables simulation and allows you to enter an 8-bit integer value and status. |
SP_D |
None |
The discrete target block output value (setpoint). |
ST_REV |
None |
The revision level of the static data associated with the function block. To support tracking changes in static parameter fields, the associated block's static revision parameter is incremented each time a static parameter field value is changed. Also, the associated block's static revision parameter is incremented if a static parameter field is written but the value is not changed. |
STATUS_OPTS |
None |
|
STRATEGY |
None |
Used to identify groupings of blocks. This data is not checked or processed by the block. |
XD_STATE |
None |
Index to the text describing the states of a discrete for the value obtained from the transducer. |
Default values and data type information for the parameters are available by expanding the Parameter View window.