The following table lists the system parameters for the Limit function block:
Parameter |
Units |
Description |
|---|---|---|
IN |
Determined by source |
The analog input value and status. |
LIM_INDICATOR |
None |
Discrete output value set True (1) when IN is limited to OUT_HI_LIM. It remains True until IN becomes limited by OUT_LO_LIM. |
OUT |
Determined by IN |
The analog output value and status. |
OUT_HI_ACT |
None |
Boolean value set True when the input is limited to the maximum value. |
OUT_HI_LIM |
Determined by IN |
The maximum output value allowed. |
OUT_LO_ACT |
None |
Boolean value set True when the input is limited to the minimum value. |
OUT_LO_LIM |
Determined by IN |
The minimum output value allowed. |
Default values and data type information for the parameters are available by expanding the Parameter View window.