Analog Control Blocks > Ramp function block

Ramp function block parameters

The following table lists the system parameters for the Ramp function block:

Table: Ramp function block system parameters

Parameter

Units

Description

COMPLETE

None

Indicates that ramp calculation is complete.

ENABLE

None

The discrete input value and status that activates ramp calculation. The discrete input value and status that enables/ disables the ramp state machine and may activate ramping or alarm calculations.

END_VALUE

EU of IN

The ramp endpoint input value and status.

IN

Determined by source

The analog input value and status that can be used as the ramp starting point.

OUT

EU of IN

The analog output value and status.

PAUSE

None

The discrete input value and status that stops ramp calculation. OUT and TIME_REMAIN are held at their last values.

RAMP_RATE

EU of IN per second

The increase or decrease rate of ramp calculation.

RAMP_TIME

Seconds

The time period for the output to ramp from IN to END_VALUE.

RAMP_TYPE

None

The variable used for ramp calculation (False [0] = RAMP_TIME, True [1] = RAMP_RATE).

TIME_REMAIN

Seconds

The time left until COMPLETE transitions to TRUE.

TRK_IN_D

None

Initiates the output tracking function (True [1] = active, False [0] = inactive).

Note