The following table lists the system parameters for the Ramp function block:
|
Parameter |
Units |
Description |
|---|---|---|
|
COMPLETE |
None |
Indicates that ramp calculation is complete. |
|
ENABLE |
None |
The discrete input value and status that activates ramp calculation. The discrete input value and status that enables/ disables the ramp state machine and may activate ramping or alarm calculations. |
|
END_VALUE |
EU of IN |
The ramp endpoint input value and status. |
|
IN |
Determined by source |
The analog input value and status that can be used as the ramp starting point. |
|
OUT |
EU of IN |
The analog output value and status. |
|
PAUSE |
None |
The discrete input value and status that stops ramp calculation. OUT and TIME_REMAIN are held at their last values. |
|
RAMP_RATE |
EU of IN per second |
The increase or decrease rate of ramp calculation. |
|
RAMP_TIME |
Seconds |
The time period for the output to ramp from IN to END_VALUE. |
|
RAMP_TYPE |
None |
The variable used for ramp calculation (False [0] = RAMP_TIME, True [1] = RAMP_RATE). |
|
TIME_REMAIN |
Seconds |
The time left until COMPLETE transitions to TRUE. |
|
TRK_IN_D |
None |
Initiates the output tracking function (True [1] = active, False [0] = inactive). |
Default values and data type information for the parameters are available by expanding the Parameter View window.