I/O Blocks > Tag Analog Input (TAGAI) function block

Tag Analog Input (TAGAI) function block PLC tag parameter mapping

The following table describes how the PLC control tag parameters map to the TAGAI function block parameters.

Table: Tag Analog Input function block PLC tag parameter mapping

PLC Control Tag Parameter

Function Block Parameter

Data Type

Cfg_EU

EUSTR

Wchar string with Status

Cfg_PVEUMax

EUMAX

Floating Point with Status

Cfg_PVEUMin

EUMIN

Floating Point with Status

PSet_HiHiLim

DEV_HIHILIM

Floating Point with Status

PSet_HiLim

DEV_HILIM

Floating Point with Status

PSet_LoLim

DEV_LOLIM

Floating Point with Status

PSet_LoLoLim

DEV_LOLOLIM

Floating Point with Status

SrcQ

STATUS

8-bit signed integer with Status

Val

OUT

Floating Point with Status