Change an on-line SIS parameter with Electronic Signature enabled
This procedure assumes:
- An SIS module is assigned to a Logic Solver that is assigned to a simulated Logic Solver Card under the ProfessionalPLUS workstation.
- The module is open in Debug mode in Control Studio.
- The module has an Electronic Signature Policy defined.
- Navigate to a block in the SIS module and select a parameter.
- Right-click, and then select Force Input.
- Enter a value in the Parameter Properties dialog, and then click OK.
- Enter a User Name, Password, and Comment in the Electronic Signature dialog, and then click OK.
- Click Confirm in the Confirmation dialog.