To transfer data from one SIS module to another, you must configure a Secure Parameter and a Secure Parameter Reference. This pair (parameter and reference) is required whether the SIS modules are assigned to the same Logic Solver or different Logic Solvers. If you are using simulated Logic Solver cards on a ProfessionalPLUS workstation, both SIS modules (the one containing the Secure Parameter and the one containing the Secure Parameter Reference) must reside on the same ProfessionalPLUS workstation in order for communication to take place.
Only Boolean data can be transferred between SIS modules; floating point and integer data cannot be transferred using the secure parameter and reference. Multiple Secure Parameter References can refer to the same Secure Parameter.
This procedure assumes an SIS module named SOURCE is open in Control Studio and you want to transfer data from it to an existing SIS module, DEST.