What's the difference between Operator Keyboard and DeltaV Operate on multiple monitors? > About Operator Keyboard > Operator Keyboard module, function block, and device faceplates > Function block faceplate reference for Operator Keyboard

Analog Input function block Operator Keyboard faceplate (AI_FB_FP_KB)

Figure: DeltaV Operate View of the Analog Input Function Block Operator Keyboard Faceplate (AI_FB_FP_KB)

The Analog Input Function Block Operator Keyboard faceplate contains the following items:

  • OUT bar graph – This graph indicates the value of the PV parameter for the AI.

  • PV – This field displays the PV value of the AI block in yellow. The background color of the field changes from black to orange (bad) or red (uncertain) when the PV status becomes bad or uncertain.

    The PV value is visible in the decimal format provided by PV_SCALE.DECPT.

  • Trend Display button – This button is used to open the trend display for the AI block. A trend display is a popup picture that shows a one second trend trace for each of the module's main operating parameters. The trend traces start when the picture is opened and stop when it is closed.

  • Module Faceplate button - This button is used to open the module faceplate display.