Rosemount Statistical Process Monitoring detail display (RMT_SPM_DT)

Limits (RMT_SPM_DT)

These fields are used to specify the limits for module alarms. Each of the alarms is assigned to one of the function blocks in the module: AI1 (PV), MEAN, STDEV, and CV. Note that the alarm limits set within the module may be different than alert limits internal to a transmitter with SPM.
  • Hi Hi Lim - This field displays the maximum value of the PV in engineering units before the high high limit active bit (HI_HI_ACT for the AI1 function block) is set. Click this field to enter a new limit.
  • Hi Lim - This field displays the maximum value of the PV in engineering units before the high limit active bit (HI_ACT for the AI1 function block) is set. Click this field to enter a new limit.
  • Lo Lim - This field displays the minimum value of the PV in engineering units before the low limit active bit (LO_ACT for the AI1 function block) is set. Click this field to enter a new limit.
  • Lo Lo Lim - This field displays the minimum value of the PV in engineering units before the low low limit active bit (LO_LO_ACT for the AI1 function block) is set. Click this field to enter a new limit.
  • Alm Hysteresis - This field displays the alarm hysteresis (or deadband) value for the PV (AI1) alarms in % of PV Scale. Click this field to enter a new value. An alarm does not recur until the PV has backed away from the corresponding limit by at least the % of PV Scale specified by this value.
  • Low Cutoff - Activated when the Low Cutoff I/O option for the AI1 function block is enabled. When the converted measurement is below the LOW_CUT value, it is shown in the PV as 0.0.
  • Mean Hi Lim - This field displays the maximum value of the Mean in engineering units before the high limit active bit (HI_ACT for the MEAN function block) is set. Click this field to enter a new limit.
  • Mean Lo Lim - This field displays the minimum value of the Mean in engineering units before the low limit active bit (LO_ACT for the MEAN function block) is set. Click this field to enter a new limit.
  • Mean Alm Hysts - This field displays the alarm hysteresis (or deadband) value for MEAN alarms in % of Mean Scale. Click this field to enter a new value. An alarm does not recur until the Mean has backed away from the corresponding limit by at least the % of Mean Scale specified by this value.
  • Std Dev Hi Lim - This field displays the maximum value of the Standard Deviation in engineering units before the high limit active bit (HI_ACT for the STDEV function block) is set. Click this field to enter a new limit.
  • Std Dev Lo Lim - This field displays the minimum value of the Standard Deviation in engineering units before the low limit active bit (LO_ACT for the STDEV function block) is set. Click this field to enter a new limit.
  • Std Dev Alm Hysts - This field displays the alarm hysteresis (or deadband) value for the STDEV alarms in % of Standard Deviation Scale. Click this field to enter a new value. An alarm does not recur until the Standard Deviation has backed away from the corresponding limit by at least the % of Standard Deviation Scale specified by this value.
  • CV Hi Lim - This field displays the maximum value of the Coefficient of Variation (CV) in engineering units before the high limit active bit (HI_ACT for the CV function block) is set. Click this field to enter a new limit.
  • CV Lo Lim - This field displays the minimum value of the CV in engineering units before the low limit active bit (LO_ACT for the CV function block) is set. Click this field to enter a new limit.
  • CV Alm Hysts - This field displays the alarm hysteresis (or deadband) value for the CV alarms in % of CV Scale. Click this field to enter a new value. An alarm does not recur until the CV has backed away from the corresponding limit by at least the % of CV Scale specified by this value.