Warning:
For blocks assigned to non-bus
I/O cards
(excluding PROVOX and RS3 I/O), only the
channels that have been modified will be affected by a download. All other
channels will hold their values and status during the download to prevent
disruption to the I/O. For blocks tied to bus cards (AS-I, DeviceNet, H1
fieldbus, Profibus DP, Serial), a download can potentially bump the I/O and
cause the controller to hold values. To prevent bumped I/O or held values
during a download, place the block producing the output in Manual mode before
downloading. Be sure to determine if the process can withstand this temporary
disruption. To ensure the safety of the process, it might be necessary to delay
the download of the configuration changes until the process can be shut down.