MASTER_SWITCH
|
The MPC/LOCAL switch of the block:
-
0=Local control
-
1=MPC control
When written to, switches all downstream blocks simultaneously.
Every write to this parameter is a write to the target mode of
all downstream blocks.
Note
Do not write every scan; doing so would prevent the operator
from changing the downstream blocks' target mode.
|
|
MASTER_SWITCH_MV[1…40]
|
The MPC/LOCAL switch for each MV.
|
|
PREDICTION[1…80][1…10]
|
For each process output, an approximated trajectory is
communicated by the block. (Approximated is defined as ten points (of 120)
where 10 is the last point in the future prediction.) For example:
-
Read PREDICTION[3][10] to observe the last point of the
prediction of PROC_OUT[3].
-
Read PREDICTION[1][5] to observe a point approximately half
way into the prediction of PROC_OUT1.
|
|
AV_HI_LIMIT[1…80]
|
The constraint high limit.
|
|
AV_LO_LIMIT[1…80]
|
The constraint low limit.
|
|
SP_HI_LIMIT[1…80]
|
The setpoint high limit. A setpoint entry that is higher than
this limit is truncated to the limit value.
|
|
SP_LO_LIMIT[1…80]
|
The setpoint low limit. A setpoint entry that is lower than this
limit is truncated to the limit value.
|
|
SP_DELTA_RANGE[1…80]
|
The setpoint range that is the maximum amount that the optimizer
can change the setpoint used in control from the operator-specified setpoint.
|
|
SP_FTIME[1…80]
|
The Response Trajectory is an exponential trajectory defined by
its filter time constant, current process output, and future required process
output (SP). Response Trajectory is used to increase stability by slowing down
the controller reaction to CV error. When unmeasured disturbances are
significant, Response Trajectory filter time constant values between 1 and 5
times the TSS are recommended.
|
|
SP_HI_RANGE[1…80]
|
A read-only parameter that presents the high limit that is
actually used by the optimizer.
|
|
SP_LO_RANGE[1…80]
|
A read-only parameter that presents the low limit that is
actually used by the optimizer.
|
|
SP_TRACKING[1…80]
|
When enabled, the SP tracks the Controlled parameter value when
the MPCPro block is in a Target mode of MAN or an Actual mode of IMAN.
-
0=SP tracking disabled
-
1=SP tracking enabled
|
|
MV_HI_LIMIT[1…40]
|
The maximum output value (in engineering units) that an operator
can enter. An entry that is greater than this limit is truncated to the limit
value.
|
|
MV_LO_LIMIT[1…40]
|
The minimum output value (in engineering units) that an operator
can enter. An entry that is lower than this limit is truncated to the limit
value.
|
|
MV_MAX_RATE[1…40]
|
The maximum rate (in engineering units per second) at which the
MPCPro function block can change the Manipulated parameter.
|
|
OPT_COST_IN[1…40] [1…5]
|
The MV cost value for optimization. [1-5] indicates the
Objective Function.
|
|
OPT_PROFIT_OUT[1…80] [1…5]
|
The output cost value for optimization. [1-5] indicates the
Objective Function.
|
|
OPT_PSV[1…40]
|
The Preferred Settling Value. This value usually represents a
valve position to which the Manipulated variable is driven if PSV is selected
under Optimization
and there are extra degrees of freedom after all
minimize/maximize optimization targets have been achieved.
|
|
OPT_TYPE_IN[1…5] [1…40]
|
The optimization type for MVs:
-
0=None
-
1=Maximize
-
2=Minimize
-
4=PSV
-
5=Equalize
[1-5] indicates the Objective Function.
|
|
OPT_TYPE_OUT[1…5] [1…80]
|
The optimization type for process outputs:
-
0=None
-
1=Maximize
-
2=Minimize
-
3=Target
[1-5] indicates the Objective Function.
|
|
OPT_OBJ_INDEX
|
The currently selected Objective Function (values are 1-5).
|
|
SIM_COUNTDOWN[1…80]
|
Shows how long (in seconds) a particular process output is
simulated before Manual mode or Shed of downstream blocks occurs. Read-only.
|
|
INPUT_DISABLED[1…40]
|
The
Disable button the DV faceplate:
-
0=Not disabled
-
1=Disabled
|
|
OUTPUT_DISABLED[1…80]
|
The
Disable button the CV and AV faceplates:
-
0=Not disabled
-
1=Disabled
|
|
ROTATION_LIMIT[1…80]
|
The maximum accepted value of the rotation factor.
|
|
FAIL_ACTION_OUT[1…80]
|
-
0=No Action
-
2=Shed downstream modes
-
3=Manual
-
4=Simulate Manual
-
5=Simulate Shed downstream modes
|
|
FAIL_ACTION_IN[1…40]
|
-
0=No Action
-
1=Hold last good value (applies to DVs only)
-
2=Shed downstream modes
-
3=Manual
|