The following table lists the system parameters for the Boolean Fan Input function block:
Parameter |
Units |
Description |
|---|---|---|
ARM_TRAP |
None |
When non-zero, ARM_TRAP enables the first out trap mechanism. |
BCD |
None |
The binary coded decimal representation of the discrete inputs. |
FIRST_OUT |
None |
A snapshot of OUT_INT when OUT_INT transitions from zero to non-zero while ARM_TRAP is non-zero. |
IN_D1 to IN_D16 |
None |
The discrete input values and statuses. The number of inputs is an extensible parameter. |
OUT_D |
None |
The output value that represents the logical OR of the discrete inputs. |
OUT_INT |
None |
The unsigned 32-bit binary weighted output value that represents the bit combination of the inputs. |
RESET_IN |
None |
When non-zero, RESET_IN clears FIRST_OUT. The block sets RESET_IN back to zero at the end of each scan. RESET_IN does not re-arm the trap. FIRST_OUT remains cleared until one or more inputs are set after all inputs are zero. |
Default values and data type information for the parameters are available by expanding the Parameter View window.