The following table lists the system parameters for the Fieldbus Multiple Discrete Input function block.
Parameter |
Units |
Description |
|---|---|---|
ABNORM_ACTIVE |
None |
The indication that a block error condition not selected in BAD_MASK is True (Active). |
ALERT_KEY |
None |
A user-assigned identification number reported in alarm messages from the block that allows HMI applications to sort and filter alarms and events. Set this parameter for each function block to indicate the physical unit the function block is associated with. This information can be used in the host for sorting alarms, and so on. |
BAD_ACTIVE |
None |
The indication that a block error condition selected in BAD_MASK is True (Active). |
BAD_MASK |
None |
The set of active error conditions that triggers a user-defined Bad condition. The user selects a subset of block error (BLOCK_ERR) conditions in the BAD_MASK parameter. When any of these conditions are True, the BAD_ACTIVE parameter becomes True. When any of the BLOCK_ERR conditions that are not included in BAD_MASK are True, ABNORM_ACTIVE becomes True. |
BLOCK_ERR |
None |
|
CHANNEL |
None |
The number of the logical hardware channel that is connected to the I/O block. It defines the transducer to be used going to or from the physical world. |
MODE |
None |
The mode record of the block. Contains the actual, target, permitted, and normal modes. |
OUT_Dn where n=1 through 8 |
None |
The discrete output value and status. |
ST_REV |
None |
The revision level of the static data associated with the function block. To support tracking changes in static parameter fields, the associated block's static revision parameter is incremented each time a static parameter field value is changed. Also, the associated block's static revision parameter is incremented if a static parameter field is written ,but the value is not changed. |
STRATEGY |
None |
Used to identify groupings of blocks. This data is not checked or processed by the block. |
SUBSTITUTE_IN_D |
None |
The substituted (from a field device) discrete input value and status. This parameter is used to provide user-entered value and status to OUT_Dn when either the device placeholder is not commissioned or the device is not communicating with the H1 card. |
Default values and data type information for the parameters are available by expanding the Parameter View window.