ABNORM_ACTIVE
|
None
|
The indication that a block error condition not selected in BAD_MASK is True (Active).
|
ALERT_KEY
|
None
|
A user-assigned identification number reported in alarm messages from the block that allows HMI applications to sort and filter alarms and events. Set this parameter for each function block to indicate the physical unit the function block is associated with. This information can be used in the host for sorting alarms, and so on.
|
BAD_ACTIVE
|
None
|
The indication that a block error condition selected in BAD_MASK is True (Active).
|
BAD_MASK
|
None
|
The set of active error conditions that triggers a user-defined Bad condition. The user selects a subset of block error (BLOCK_ERR) conditions in the BAD_MASK parameter. When any of these conditions are True, the BAD_ACTIVE parameter becomes True. When any of the BLOCK_ERR conditions that are not included in BAD_MASK are True, ABNORM_ACTIVE becomes True.
|
BLOCK_ERR
|
None
|
The summary of active error conditions associated with the block. The possible block errors for the H1 Carrier Multiple Discrete Input function block are:
|
CHANNEL
|
None
|
The number of the logical hardware channel that is connected to the I/O block. It defines the transducer to be used going to or from the physical world.
|
FIELD_VAL_D
|
None
|
The 8-bit integer value and status of the discrete input from the H1 carrier.
|
IO_OPTS
|
None
|
I/O options allow you to select options for I/O value processing. The only supported I/O option is:
|
MODE
|
None
|
The mode record of the block. Contains the actual, target, permitted, and normal modes.
|
OUT_INT
|
None
|
The 8-bit integer output value and status.
|
PV_D
|
None
|
The 8-bit integer process variable used in block execution.
|
PV_FTIME
|
Seconds
|
The time that each bit of FIELD_VAL_D must be on or off before the corresponding bit of PV_D changes.
|
SIMULATE_D
|
None
|
Enables simulation and allows you to enter a discrete value and status.
|
ST_REV
|
None
|
The revision level of the static data associated with the function block. To support tracking changes in static parameter fields, the associated block's static revision parameter is incremented each time a static parameter field value is changed. Also, the associated block's static revision parameter is incremented if a static parameter field is written ,but the value is not changed.
|
STATUS_OPTS
|
None
|
Status options allow you to select options for status handling and processing. The available status options for this block are:
|
STRATEGY
|
None
|
Used to identify groupings of blocks. This data is not checked or processed by the block.
|
SUBSTITUTE_IN_D
|
None
|
The substituted (from a field device) discrete input value and status. This parameter is used to provide user-entered value and status to OUT_INT when either the device placeholder is not commissioned or the device is not communicating with the H1 card.
|
XD_STATE
|
None
|
Index to the text describing the states of a discrete for the value obtained from the transducer.
|