Analog Control Blocks > Limit function block

Limit function block parameters

The following table lists the system parameters for the Limit function block:

Table: Limit function block system parameters

Parameter

Units

Description

IN

Determined by source

The analog input value and status.

LIM_INDICATOR

None

Discrete output value set True (1) when IN is limited to OUT_HI_LIM. It remains True until IN becomes limited by OUT_LO_LIM.

OUT

Determined by IN

The analog output value and status.

OUT_HI_ACT

None

Boolean value set True when the input is limited to the maximum value.

OUT_HI_LIM

Determined by IN

The maximum output value allowed.

OUT_LO_ACT

None

Boolean value set True when the input is limited to the minimum value.

OUT_LO_LIM

Determined by IN

The minimum output value allowed.

Note

Default values and data type information for the parameters are available by expanding the Parameter View window.