ABNORM_ACTIVE
|
None
|
The indication that a block error condition not selected in
BAD_MASK (on the function block level) is True (Active).
|
|
ALARM_HYS
|
Percent of PV_SCALE
|
The amount the alarm value must return within the alarm limit
before the associated active alarm condition clears. ALARM_HYS is limited to
50% of scale.
|
|
BAD_ACTIVE
|
None
|
The indication that a block error condition selected in
BAD_MASK (at the function block level) is True (Active).
|
|
BAD_MASK
|
None
|
The set of active error conditions that triggers a
user-defined Bad condition. The user selects a subset of block error
(BLOCK_ERR) conditions in the BAD_MASK parameter. When any of these conditions
are True, the BAD_ACTIVE parameter becomes True. When any of the BLOCK_ERR
conditions that are not included in BAD_MASK are True, ABNORM_ACTIVE becomes
True.
|
|
BAL_TIME
|
Seconds
|
Specifies the time for dissipation of the internal balancing
bias.
|
|
BKCAL_IN
|
EU of OUT_SCALE
|
The analog input value and status from another block's
BKCAL_OUT output that is used by an upstream block for bumpless transfer.
|
|
BKCAL_OUT
|
EU of PV_SCALE
|
The value and status required by the BKCAL_IN input of another
block to prevent reset windup and provide bumpless transfer to closed loop
control.
|
|
BLOCK_ERR
|
None
|
The summary of active error conditions associated with the
block. The possible block errors for the Ratio function block are:
-
Out of Service
-
Local Override
-
Input Failure/Bad PV
|
|
CAS_IN
|
EU of PV_SCALE
|
The remote setpoint value from another block.
|
|
CONTROL_OPTS
|
None
|
Control options allow you to specify control strategy options.
The valid control options are:
-
No OUT Limits in Manual
-
Obey SP lim if Cas or RCas
-
Use BKCAL_OUT With IN_1
-
Act on IR
-
Use PV for BKCAL_OUT
-
Track in Manual
-
Track Enable
-
SP Track Retained Target
-
SP-PV Track in LO or IMan
-
SP-PV Track in Man.
|
|
DV_HI_ACT
|
None
|
The result of alarm detection associated with DV_HI_LIM. If
DV_HI_ACT equals True, DV_HI_LIM has been exceeded.
|
|
DV_HI_LIM
|
EU of PV_SCALE
|
The amount by which PV can deviate above SP before the
deviation high alarm is triggered. The magnitude of DV_HI_LIM cannot be greater
than the range of PV_SCALE. When this limit is exceeded, DV_HI_ACT is set to
True. The deviation of PV is above SP.
|
|
DV_LO_ACT
|
None
|
The result of alarm detection associated with DV_LO_LIM. If
DV_LO_ACT equals True, DV_LO_LIM has been exceeded.
|
|
DV_LO_LIM
|
EU of PV_SCALE
|
The amount by which PV can deviate below SP before the
deviation low alarm is triggered. The magnitude of DV_LO_LIM cannot be greater
than the range of PV_SCALE. When this limit is exceeded, DV_LO_ACT is set to
True. Note that DV_LO_LIM is a negative number and is compared against PV – SP.
|
|
FRSIRB_OPTS
|
None
|
The FRSI add-on I/O option supported is Treat_IN_1 as wild.
|
|
GAIN
|
None
|
The multiplier used to scale the ratio value.
|
|
HI_ACT
|
None
|
The result of alarm detection associated with HI_LIM. If
HI_ACT equals True, HI_LIM has been exceeded.
|
|
HI_HI_ACT
|
None
|
The result of alarm detection associated with HI_HI_LIM. If
HI_HI_ACT equals True, HI_HI_LIM has been exceeded.
|
|
HI_HI_LIM
|
EU of PV_SCALE
|
The setting for the alarm limit used to detect the high high
alarm condition.
|
|
HI_LIM
|
EU of PV_SCALE
|
The setting for the alarm limit used to detect the high alarm
condition.
|
|
IN
|
Defined by supplying block
|
The analog input value and status used with IN_1 to calculate
PV.
|
|
IN_1
|
Defined by supplying block
|
The analog input value and status used to calculate OUT.
|
|
INSPECT_ACT
|
None
|
Indicates if Inspect is enabled and one or more of the limits
for the block have been exceeded. The normal value is 0. This parameter is set
to 1 only if both of the following conditions are true:
-
The
Write to Inspect Alarm context menu
item has been selected from Inspect for this block.
-
With the Current Hour filter selected, Inspect indicates
that an abnormal condition exists for Mode, Control, Input, or Variability.
(Note that an abnormal condition exists for Variability only if both the
Variability Index and the Standard Deviation have exceeded their defined
limits.)
|
|
LO_ACT
|
None
|
The result of alarm detection associated with LO_LIM. If
LO_ACT equals True, LO_LIM has been exceeded.
|
|
LO_LIM
|
EU of PV_SCALE
|
The setting for the alarm limit used to detect the low alarm
condition.
|
|
LO_LO_ACT
|
None
|
The result of alarm detection associated with LO_LO_LIM. If
LO_LO_ACT equals True, LO_LO_LIM has been exceeded.
|
|
LO_LO_LIM
|
EU of PV_SCALE
|
The setting for the alarm limit used to detect the low low
alarm condition.
|
|
MODE
|
None
|
Parameter used to request, show, and set the block operating
state.
|
|
OUT
|
EU of OUT_SCALE
|
The analog output value and status.
|
|
OUT_HI_LIM
|
EU of OUT_SCALE
|
The maximum output value allowed.
|
|
OUT_LO_LIM
|
EU of OUT_SCALE
|
The minimum output value allowed.
|
|
OUT_SCALE
|
None
|
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point associated with OUT.
|
|
PV
|
EU of PV_SCALE
|
The process variable used in block execution and alarm limit
detection.
|
|
PV_FTIME
|
Seconds
|
The time constant of the first-order PV filter applied to IN.
It is the time required for a 63% change in IN.
|
|
PV_SCALE
|
None
|
The high and low scale values, the engineering units code, and
the number of digits to the right of the decimal point associated with PV.
|
|
RA_FTIME
|
Seconds
|
The time constant of the first-order ratio filter applied to
IN_1. It is the time required for a 63% change in IN_1.
|
|
RCAS_IN
|
EU of SP_SCALE
|
The remote analog setpoint value and status. Input provided by
a device or the output of another block.
|
|
RCAS_OUT
|
EU of PV_SCALE
|
The output provided for bumpless mode transfer and reset
limiting by the source of RCAS_IN. Essentially the equivalent of BKCAL_OUT for
RCAS_IN.
|
|
SHED_OPT
|
None
|
Defines action to be taken on remote control device time out.
|
|
SHED_TIME
|
Seconds
|
The maximum allowable time between RCAS_IN and ROUT_IN
updates. If exceeded, mode shedding takes place.
|
|
SP
|
EU of PV_SCALE
|
The block's setpoint value.
|
|
SP_HI_LIM
|
EU of PV_SCALE
|
The highest setpoint value allowed.
|
|
SP_LO_LIM
|
EU of PV_SCALE
|
The lowest setpoint value allowed.
|
|
SP_RATE_DN
|
EU of PV_SCALE per second
|
Ramp rate at which downward setpoint changes are acted on in
Auto mode, in PV units per second. If the ramp rate is set to 0.0, then the
setpoint is used immediately. For control blocks, rate limiting applies only in
Auto. For output blocks, rate limiting applies in Auto, Cas, and RCas modes.
|
|
SP_RATE_UP
|
EU of PV_SCALE per second
|
Ramp rate at which upward setpoint changes are acted on in
Auto mode, in PV units per second. If the ramp rate is set to 0.0, then the
setpoint is used immediately. For control blocks, rate limiting applies only in
Auto. For output blocks, rate limiting applies in Auto, Cas, and RCas modes.
|
|
SP_WRK
|
EU of PV_SCALE
|
The working setpoint of the block. It is the result of
setpoint limiting and setpoint rate of change limiting.
|
|
STATUS_OPTS
|
None
|
Status options allow you to select options for status handling
and processing. The supported status options are:
-
Target to Manual if Bad IN
-
Use Uncertain as Good
-
IFS if Bad CAS_IN
-
IFS if Bad IN.
|
|
STDEV
|
EU of OUT_SCALE or EU of PV_SCALE
(reports in percent to Inspect)
|
The standard deviation of PV. For analog control blocks in
AUTO, mean is assumed to be the SP.
|
|
STDEV_CAP
|
EU of OUT_SCALE or EU of PV_SCALE
(reports in percent to Inspect)
|
The estimated capability standard deviation (measurement of
short term variation). An estimate of the least standard deviation the process
could achieve ideally.
|
|
STDEV_TIME
|
Seconds
|
The time frame over which STDEV and STDEV_CAP are performed.
The default value of zero is good for most processes where the scan rate is no
more than approximately 10 times faster than the time to steady state.
If the process is relatively much slower, it is recommended
that you enter the approximate time it takes for the process to return to
steady state after a change. This ensures that the STDEV and STDEV_CAP
calculations accurately consider the actual time constant of the process.
|
|
TRK_IN_D
|
None
|
Discrete input that initiates the external tracking function.
|
|
TRK_SCALE
|
None
|
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point associated with the external
tracking value (TRK_VAL).
|
|
TRK_VAL
|
EU of TRK_SCALE
|
The analog input used in the external tracking function.
|