The following table lists the system parameters for the Signal Characterizer function block:
Parameter |
Units |
Description |
|---|---|---|
ABNORM_ACTIVE |
None |
The indication that a block error condition not selected in BAD_MASK (on the function block level) is True (Active) or the indication that an error condition (at the module level) not selected in MERROR_MASK is True (Active) or a module status not selected in MSTATUS_MASK is True (Active). |
ALERT_KEY(1) |
None |
A user-assigned identification number reported in alarm messages from the block that allows HMI applications to sort and filter alarms and events. Set this parameter for each function block to indicate the physical unit the function block is associated with. This information can be used in the host for sorting alarms, and so on. |
BAD_ACTIVE |
None |
The indication that a block error condition selected in BAD_MASK (at the function block level) is True (Active) or the indication that an error condition (at the module level) selected in MERROR_MASK is True (Active) or a module status selected in MSTATUS_MASK is True (Active). |
BAD_MASK |
None |
The set of active error conditions that triggers a user-defined Bad condition. The user selects a subset of block error (BLOCK_ERR) conditions in the BAD_MASK parameter. When any of these conditions are True, the BAD_ACTIVE parameter becomes True. When any of the BLOCK_ERR conditions that are not included in BAD_MASK are True, ABNORM_ACTIVE becomes True. |
BLOCK_ERR |
None |
The summary of active error conditions associated with the block. The possible block errors for the Signal Characterizer function block are: |
BYPASS |
None |
When BYPASS is enabled in the Signal Characterizer function block, it bypasses the signal characterization. OUT_1 equals IN_1 and OUT_2 equals IN_2. To enable BYPASS, set the BYPASS parameter to On and select the CONTROL_OPTS Bypass Enable option. |
CONTROL_OPTS |
None |
Control options allow you to specify control strategy options. The supported control option for the Signal Characterizer function block is: |
CURVE_X |
Determined by source |
The array of input curve values (as many as 21 points). |
CURVE_Y |
Determined by source |
The array of output curve values (as many as 21 points). |
IN_1 |
Determined by source |
The first analog input value and status. |
IN_2 |
Determined by source |
The second analog input value and status. |
MODE |
None |
The mode record of the block. Contains the actual, target, permitted, and normal modes. |
OUT_1 |
EU of IN |
The analog output value and status related to IN_1. |
OUT_2 |
EU of IN |
The analog output value and status related to IN_2. |
ST_REV(1) |
None |
The revision level of the static data associated with the function block. To support tracking changes in static parameter fields, the associated block's static revision parameter is incremented each time a static parameter field value is changed. Also, the associated block's static revision parameter is incremented if a static parameter field is written but the value is not changed. |
STRATEGY(1) |
None |
Used to identify groupings of blocks. This data is not checked or processed by the block. |
SWAP_2 |
None |
Swaps the X and Y axes used for OUT_2. |
Default values and data type information for the parameters are available by expanding the Parameter View window.