Controller considerations > Preserving configuration and controller data during power loss

Restart diagnostic parameters

The controller supports the following diagnostic parameters related to power failure and restart. Unless otherwise specified, they are available through the DeltaV Diagnostics application:

Note

The value of the LastPfDur or SecsLastPf parameter is valid and meaningful only after a power failure—that is, when the value of the PfCount parameter is equal to or greater than 1. The reported value of the LastPfDur or SecsLastPf parameter is not accurate, for example, following first download, after a switchover, or after the standby controller is reseated with the Cold Restart option enabled because all of these conditions are accompanied by a PfCount value of 0.