Active 3.3 VDC Error
|
WIOC: Internal problem with
current active WIOC. The WIOC needs to be replaced.
|
|
Active Commissioning Module Error
|
WIOC: The Active unit might not commission properly after a
reboot, commissioning data might be lost or corrupted. The cause of the problem
is internal.
|
|
Active Primary 24 VDC Error
|
Power supply loss detected with the active’s primary supply.
Check connection or replace power supply.
|
|
Active Primary I/O Port Error
|
WIOC: Active Unit unable to communicate on primary ACN.
|
|
Active Primary Temperature Error
|
WIOC: The active unit's primary temperature sensor is too
high or too low.
|
|
Active RTC Error
|
The Real Time Clock is not working properly. System time
might not be set properly.
|
|
Active Secondary 24 VDC Error
|
Power supply loss detected with the active's secondary
supply. Check connection or replace power supply.
|
|
Active Secondary I/O Port Error
|
WIOC: Active Unit unable to communicate on secondary ACN.
|
|
Active Secondary Temperature Error
|
WIOC: The active unit's secondary temperature sensor is too
high or too low.
|
|
Active Temperature Error
|
CIOC: The active unit's temperature is too high or low.
|
|
Assignment Mismatch - Remote Node
ID,
card_type Card, Cnn
|
The controller needs to be downloaded because the remote I/O
card in slot Cnn, which was previously assigned to this controller, has
been reassigned to a different controller.
|
|
Assignment Mismatch - Remote Node
node_name,
card_type Card, Cnn
|
The controller needs to be downloaded because the remote I/O
card in slot Cnn, which was previously assigned to this controller, has
been reassigned to a different controller.
|
|
Assignment Mismatch - with
CIOC
|
Perform setup data download of the controller. The CHARM I/O
card (for example,
CIOC-2), that was previously assigned to this
controller, has now been unassigned.
|
|
Assignment Mismatch - Node Id
|
Perform setup data download of the controller. The CHARM I/O
card (for example, CIOC ID
2517893127), , that was previously assigned to this
controller, has now been unassigned.
|
|
Card in Failsafe Mode -
card_type Card, Cnn
|
The simplex I/O card in slot Cnn is in failsafe mode
and driving any outputs to the configured failsafe value.
|
|
CHARM Bus Terminator Error
|
The terminator on the CHARM bus is missing or broken.
|
|
CHARMs Simulation Enabled
|
CHARMs simulation has been enabled through DeltaV Explorer.
The value coming from the I/O device is being disregarded.
|
|
Configuration Error -
card_type Card, Cnn
|
An invalid configuration has been detected for the I/O card
in slot Cnn.
|
|
Database Space - Allocated database space low,
value% free
|
The amount of free space in the folder allocated for Batch
Historian database storage has fallen below 10%.
You can increase the maximum size of the Batch Historian
database storage folder in DeltaV Explorer by navigating to the
Output tab on the
Batch Historian Properties dialog for
this workstation, selecting a location in the Directory Path column, and
clicking
Modify.
|
|
Direct Link Unavailable
|
The Redundant Batch system's Direct Link
connection is unavailable. This connection is through an Ethernet card in both
the active and standby computers.
|
|
Hardware Error -
card_type Card, Cnn
|
A hardware error preventing reliable operation has been
detected for the simplex or redundant I/O card in slot Cnn.
|
|
Hardware Error -
card_type Card, Cnn, Pnn
|
A communications problem has been detected at port
Pnn of the I/O card in slot Cnn.
|
|
HART Connection For
CIOC Is Unbound- Perform Setup Data Download
|
The binding between the CHARM I/O card (for example,
CIOC-2) and the controller for receiving HART data is
bad. Setup data download needs to be performed. Without the setup data
download, there will be no communication between the CHARM I/O card and the
controller.
|
|
HART Connection For Node Id:%u Is Unbound - Perform Setup
Data Download
|
The binding between the CHARM I/O card (for example, CIOC ID
2517893127) and the controller for receiving HART data
is bad. Setup data download needs to be performed. Without the setup data
download, there will be no communication between the CHARM I/O card and the
controller.
|
|
Initialization Error -
card_type Card, Cnn, Pnn
|
The AS-Interface I/O card in slot Cnn failed to
initialize port Pnn after receiving configuration data.
|
|
Network Integrity Error - Primary Network
|
All communications attempts between a node on the primary
network and all other nodes in the system have failed. There is no
communications on this network interface.
|
|
Network Integrity Error - Secondary Network
|
All communications attempts between a node on the secondary
network and all other nodes in the system have failed. There is no
communications on this network interface.
|
|
No Communications On Port -
card_type Card, Cnn, Pnn
|
A communications failure has been detected at port
Pnn of the I/O card in slot Cnn. Port communications failure
errors include the following:
-
A port cannot communicate with any devices connected to
it.
-
A loss of power to the segment connected to the port.
-
The I/O card has detected an error with the port’s
communications chip.
-
A port on an H1 fieldbus card cannot communicate with
any devices connected to it, including the standby H1 card in a redundant
configuration.
|
|
NON-HART Connection For
CIOC Is Unbound- Perform Setup Data Download
|
The binding between the CHARM I/O card (for example,
CIOC-2) and the controller for receiving non-HART data
is bad. Setup data download needs to be performed. Without the setup data
download, there will be no communication between the CHARM I/O card and the
controller.
|
|
NON-HART Connection For Node Id:
nn Is Unbound - Perform Setup Data Download
|
The binding between the CHARM I/O card (for example, CIOC ID
2517893127) and the controller for receiving non-HART
data is bad. Setup data download needs to be performed. Without the setup data
download, there will be no communication between the CHARM I/O card and the
controller.
|
|
Not Bound - Needs Setup Data, Remote Node
ID,
card_type Card, Cnn
|
The remote I/O card in slot Cnn of the remote I/O
node has been assigned, but setup data has not been downloaded to the
controller.
|
|
Not Bound - Needs Setup Data, Remote Node
node_name,
card_type Card, Cnn
|
The remote I/O card in slot Cnn of the
node_name remote I/O node has been assigned, but setup
data has not been downloaded to the controller.
|
|
Not Communicating -
card_type Card, Cnn
|
The I/O subsystem cannot communicate with the I/O card in
slot Cnn.
|
|
Not Communicating - on Pri Zone Network
|
The local Inter-Zone Server cannot communicate with any
other zone over the primary Inter-Zone Network.
|
|
Not Communicating - on Sec Zone Network
|
The local Inter-Zone Server cannot communicate with any
other zone over the secondary Inter-Zone Network.
|
|
Not Communicating - Standby
|
A standby controller in the DeltaV network’s redundancy
subsystem is not communicating with the primary controller.
|
|
Not Communicating - with Zone
zone_name on Pri Zone Network
|
The local Inter-Zone Server cannot communicate with the
zone_name zone over the primary Inter-Zone Network.
|
|
Not Communicating - with Zone
zone_name on Sec Zone Network
|
The local Inter-Zone Server cannot communicate with the
zone_name zone over the secondary Inter-Zone Network.
|
|
Power Error -
card_type Card, Cnn, Pnn
|
A power problem, such as a loss of power to the segment
connected to the port, has been detected at port Pnn of the I/O card in
slot Cnn.
|
|
Primary Cascade Port Error
|
The primary cascade port is not communicating properly.
Replace the primary I/O port. The cause of this error is internal. Note that
this message is only displayed if the option is enabled.
|
|
Primary CHARM Bus Voltage Error
|
The left-hand CIOC has detected that primary CHARM bus power
is outside its normal operating range.
Possible causes:
- Left-hand CIOC is bad
- CHARM baseplate is bad
- One or more CHARMs are bad
- Terminator is bad
- Extender or cable is bad
- CIOC carrier is bad
|
|
Primary Commissioning Module Error
|
The unit might not commission properly after a reboot,
commissioning data might be lost or corrupted, or the primary I/O port might
need replacing. The cause of the problem is internal.
|
|
Primary I/O Port Error
|
Either a primary commissioning module error or a primary
cascade port error has been detected.
|
|
Redundancy Serial Link Error
|
The serial link between the WIOC nodes has an error. The
redundant terminal block may need to be replaced.
|
|
Secondary Cascade Port Error
|
The secondary cascade port is not communicating properly.
Replace the secondary I/O port. The cause of this error is internal.
This message is displayed even when configured as simplex
networks. This is done to ensure commissioning if an error occurs with the
primary I/O port.
|
|
Secondary CHARM Bus Voltage Error
|
The right-hand CIOC has detected that secondary CHARM bus
power is outside its normal operating range.
Possible causes:
- Right-hand CIOC is bad
- CHARM baseplate is bad
- One or more CHARMs are bad
- Terminator is bad
- Extender or cable is bad
- CIOC carrier is bad
|
|
Secondary I/O Port Error
|
Either a secondary commissioning module error or a secondary
cascade port error has been detected.
|
|
Secondary Commissioning Module Error
|
The unit might not commission properly after a reboot,
commissioning data might be lost or corrupted, or the secondary I/O port might
need replacing. The cause of the problem is internal.
|
|
Standby 3.3V DC Error
|
WIOC: Internal voltage problem with the
current standby WIOC. The WIOC needs to be replaced.
|
|
Standby Card Not Available -
card_type Card, Cnn
|
The I/O card in slot Cnn is not communicating with
its redundant partner. The standby I/O card is not available for switchover.
|
|
Standby Commissioning Module Error
|
WIOC: The Standby unit might not commission properly after a
reboot, commissioning data might be lost or corrupted. The cause of the problem
is internal.
|
|
Standby Primary 24 VDC Error
|
Power supply loss detected with the standby's primary
supply. Check connection or replace power supply.
|
|
Standby Primary I/O Port Error
|
WIOC: Standby Unit unable to communicate on primary ACN.
|
|
Standby Primary Temperature Exceeded
|
WIOC: The standby unit's primary temperature sensor is too
high or low.
|
|
Standby RTC Error
|
The Real Time Clock is not working properly. System time
might not be set properly.
|
|
Standby Secondary 24 VDC Error
|
Power supply loss detected with the standby's secondary
supply. Check connection or replace power supply.
|
|
Standby Secondary I/O Port Error
|
WIOC: Standby Unit unable to communicate on secondary ACN.
|
|
Standby Secondary Temperature Exceeded
|
WIOC: The standby unit's secondary temperature sensor is too
high or low.
|
|
Standby Temperature Error
|
CIOC: The standby unit's temperature is too high or low.
|
|
Standby Unavailable
|
A standby controller in the DeltaV network’s redundancy
subsystem is not available for switchover, because its configuration
information is not valid.
|
|
Termination Error -
card_type Card, Cnn, Pnn
|
Termination is disconnected at port Pnn of the I/O
card in slot Cnn.
|