Appendix C - batch system capacities

The following tables contain the fixed and recommended capacities of the DeltaV Batch subsystem.

The values in the Fixed Limit column are limits imposed by the system that the user cannot exceed. The values in the Maximum Recommended Limit column are values that are recommended that the user not exceed and are to be used as a guideline when determining your system's performance.

It is important to note that the combination of items and the configuration of those items in a system and other variables (such as available memory in the controller and recipe or phase logic size) can effect whether or not a fixed or maximum recommended limit can be reached on a system; and, may also have an effect on the performance of a particular configuration. For example, a system may exceed the maximum recommended limit for one item without noticing any change in performance. However, if a particular configuration nears the maximum recommended limit of several items in combination, the potential for a change in performance is increased.

Table: Controller Capacities

Controller Capacities

Fixed Limit

Maximum Recommended Limit

PLMs per controller: non-redundant

Limited by available memory in the controller.

SQ, SD Plus, MQ, MD Plus controllers - 300

SX, MX controller - 600

PK controller - 1200

PLMs per controller: redundant

Limited by the minimum available memory between the redundant controllers.

SQ, SD Plus, MQ, MD Plus controllers - 300

SX, MX controller - 600

PK controller - 1200

Unit Phases running simultaneously per unit module: redundant and non-redundant controller

10

Unit phases can be marked as Always in Memory. This means that the phase is always able to be loaded so that it never fails to run because of over-commitment of controller memory resources.

10

Number of active phases in a controller

None

SQ, SD Plus, MQ, MD Plus controllers - 50

SX, MX controller - 150

PK controller - 300

Number of unit modules per controller

None

SQ, SD Plus, MQ, MD Plus controllers - 5

SX, MX controller - 24

PK controller - 48

Common phase logic algorithms in a single controller

None

SQ, SD Plus, MQ, MD Plus controllers - 200

SX, MX controller - 600

PK controller - 1200

Batch Executive System Capacities

A DeltaV system can include up to four enabled Batch Executives, four enabled Batch Historians, and four enabled Campaign Managers.

On Redundant Batch systems, a pair of Application Stations running the Batch Executive counts as one Batch Executive. Similarly, a pair of Application Stations running the Campaign Manager counts as one Campaign Manager. 

Batch Capacities

Fixed Limit

Maximum Recommended Limit

Maximum active batches, excluding manual phases

100

100

Maximum total batches (including active, complete and ready)

200

200

Maximum total campaigns per system

None

100

Recipes assigned to the Batch Executive

None

500

Phases per system (combination of unit phases and PLMs)

None

5000

Unit modules per system

None

400

Downstream unit modules per unit module

None

300

Equipment Train Classes per system

None

100

Equipment Trains per system

None

200

Unit Aliases per Equipment Train Class

None

250

Unit selection policies per system

None

100

Characters per unit selection policy

2000

2000

Phase Step actions in step (Run Logic)

None

50

Phase step assignments per action

None

50

SFC Parallel Steps (phase run logic)

None

50

PLMs assigned to a single unit

None

200

Unit phases configured per unit

None

100

Sequential steps in an operation

None

200

Parallel steps in an operation (using PLMs)

None

30

Parameters (input) per phase

99

99

Parameters (report) per phase

99

99

Recipe parameters (input) per recipe

None

1,000

Recipe parameters (report) per operation

99

99

Recipe parameters (report) per unit procedure

99

99

Recipe parameters (report) per procedure

None

500

Active phase-to-phase messages (per Batch Executive)

None

50

Active, unacknowledged operator prompts-messages

None

100

Number of formulas per recipe

None

600

Number of authorizers for a recipe

5

5

Recipe Exchange connections

4

4

Remote soft phase workstations

None

3

Remote soft phases in parallel on max remote soft phase workstations

None

65

Remote soft phases in parallel on one remote soft phase workstation

50

50

Nodes connected to the Batch Executive 1

50

50

Process cells

None

150

Concurrent # of connections for a Campaign Manager

None

15

Unit parameters per unit class

None

1000

Aliases per unit class

None

500

Number of phase algorithm parameters per phase class

None

200

Dynamic reference parameters on a unit class as unit parameter definitions

None

500

Dynamic reference parameters on a phase class as algorithm parameters

None

200

1 Nodes are counted as follows:

  • Multiple Remote Desktop Service sessions to the same workstation count as one node.

  • A workstation running both the Batch Operator Interface and a DeltaV Operate picture with the Batch controls on it counts as one node.

Batch Historian System Capacities

A DeltaV system can include up to four enabled Batch Historians.

Batch Capacities

Fixed Limit

Maximum Recommended Limit

Batch Historian database size

None

8 gigabytes