| CSLS SIS capacities | Limits |
|---|---|
|
CHARMs Smart Logic Solvers per SIS Controller (SZ) |
16 |
|
Function blocks per SIS module |
500(1) |
|
User-defined parameters per SIS module |
230 |
|
SIS modules in a CSLS |
16 |
|
Boolean Secure parameters in a CSLS |
96 |
|
Non-Boolean Secure parameters in a CSLS |
32 |
|
Non-secure parameter references in a CSLS |
96 |
|
LS CHARMs per CSLS (arranged as 8 carriers of 12 CHARMs per carrier) |
96 Note Only 48 of the 96 LS CHARM slots can be configured as output LS CHARMs. LS DVC HART DTA CHARMs are included in the output CHARMs count. This can be any combination of simplex and redundant as long as the slot count of output LS CHARMs does not exceed 48. This limit is not enforced during configuration, only during download. The remaining 48 slots can be configured as input LS CHARMs. |
|
CHARM Carriers per CSLS |
8 |
|
SIS Controller Modbus communications |
4000 mapped values |
| CSLS Global Safety Network property | Limit |
|---|---|
|
LSNB nodes per LSN |
1 |
|
Domain publishers per domain |
16 |
|
Publishers per LSNB (either type - there can be a mix of domain publishers and system publishers) |
4 |
|
System publishers per DeltaV system |
8 |
|
Listener LSNBs per domain |
No limit |
|
Boolean Secure parameters per publisher |
192 |
|
Non-Boolean Secure parameters per publisher |
64 |
|
Boolean Secure parameters received from the LSN per LSNB |
768 |
|
Non-Boolean Secure parameters received from the LSN per LSNB |
256 |
|
Boolean Secure parameters an LSNB can receive from the GSN |
3072 |
|
Non-Boolean Secure parameters an LSNB can receive from the GSN |
1024 |
| GSN Domains per system | 16 |
| Local Safety Network Gateway property | Limit |
|---|---|
|
LSNGs per local safety network |
4 (3 if the LSN contains an LSNB) |
|
Publishers per LSNG |
4 |
|
Publishers per LSN |
8 |
|
Boolean Secure parameters per publisher |
192 |
|
Boolean Secure parameters per LSNG |
768 |
|
Modbus devices per LSNG |
2 |
| Common SIS capacities | Limits |
|---|---|
|
Temporary variables defined using VAR…END_VAR per expression |
32 |
|
Function blocks in the top level of an SIS module |
127(1) |
|
Function blocks per composite |
127(1) |