Controller considerations > Online controller migration
Migrate controllers online
-
Verify that the Active and Standby LEDs on the current active and
standby controllers are steady.
-
Ensure that DeltaV Diagnostics shows no Bad Integrity on the
current controller's redundancy subsystem and on the standby controller.
-
Ensure that DeltaV Diagnostics shows that the standby controller
is present and available for switchover.
-
Replace the current standby controller with the new model standby
controller.
-
Use the DeltaV Controller and I/O Upgrade Utility to upgrade the
controller to the correct version of the DeltaV software.
-
Wait for the migrated standby controller to become reconfigured
and its LED to go to steady.
-
Ensure that DeltaV Diagnostics shows no Bad Integrity on the
current active controller's redundancy subsystem and on the standby controller.
-
Ensure that DeltaV Diagnostics shows that the standby controller
is present and available for switchover.
-
Manually initiate a controller switchover from DeltaV
Diagnostics. The newly replaced standby controller becomes the new active
controller.
-
Replace the standby controller with the new model controller.
-
Use the DeltaV Controller and I/O Upgrade Utility to upgrade the
new controller to the correct version of the DeltaV software.
-
Launch DeltaV Explorer and ensure that the controller model
displayed within controller properties have updated to the correct model for
both controllers. If the controllers' models in DeltaV Explorer have not
updated then download the Setup Data for the controller.