You can install, enable, and run the DeltaV Continuous Historian, the
default historian for DeltaV, on the following local (inside the DeltaV ACN) or remote workstations:
- Local: ProfessionalPLUS workstation,
Application Station, or Operator Station
- Remote:
Application Station or
Operator Station
You can install, enable, and run the Advanced Continuous
Historian on the following local (inside the DeltaV ACN) or
remote workstations:
- Local: Application Station
- Remote: Application Station
You can install, enable, and run OSIsoft PI Server on the
following local (inside the DeltaV ACN) or remote workstations:
- Local: Application Station
- Remote: Application Station or non-DeltaV workstation
Install and enable the DeltaV Continuous Historian
To install and enable the DeltaV Continuous Historian to
run on an Application Station:
- While installing DeltaV, select the
DeltaV Continuous Historian option in the
Select Historian dialog.
- After installing DeltaV, start DeltaV Explorer, and then navigate
to the Application Station node under
in the
DeltaV_System pane.
- Right-click
Continuous Historian, and then select
Properties to open the
General tab of the
Continuous Historian Properties dialog.
- Select the
Enabled option and the
Use DeltaV Continuous Historian option in the
Continuous Historian Selection box.
When you install DeltaV on a ProfessionalPLUS or Operator
Station, the DeltaV Continuous Historian is automatically installed by default.
To enable the DeltaV Continuous Historian after installing DeltaV:
- Start DeltaV Explorer, and then navigate to the
ProfessionalPLUS or Operator Station node under
in the
DeltaV_System pane.
- Right-click
Continuous Historian, and then select
Properties to open the
General tab of the
Continuous Historian Properties dialog.
- Select the
Enabled option.
Install and enable the Advanced Continuous Historian
To install and enable the Advanced Continuous Historian to run on an
Application Station:
- While installing DeltaV, select the
Advanced Continuous Historian option in the
Select Historian dialog.
- After installing DeltaV, start DeltaV Explorer, and then navigate
to the Application Station node under
in the
DeltaV_System pane.
- Right-click
Continuous Historian, and then select
Properties to open the
General tab of the
Continuous Historian Properties dialog.
- Select the
Enabled option and the
Use Advanced Continuous Historian option in
the
Continuous Historian Selection box.
Install and enable PI Server
To install and enable PI Server to run on an Application Station:
- While installing DeltaV, select the Enterprise Historian option in
the
Select Historian dialog.
- After installing Deltav, install PI Server on the Application
Station according to the documentation from OSIsoft.
- Start DeltaV Explorer, and then navigate to the Application Station
node under
in the
DeltaV_System pane.
- Right-click
Continuous Historian, and then select
Properties to open the
General tab of the
Continuous Historian Properties dialog.
- Select the
Enabled option and the
Use Enterprise Historian option in the
Continuous Historian Selection box.
- Configure PI Server to run on the Application Station according to
the documentation from OSIsoft.
To install and configure PI Server to run on a non-DeltaV workstation: