The channel integrity parameter (OINTEG) is True (1) when one or more of the following conditions are True:
HART card detects a problem with itself.
An open or short is detected on a HART channel input.
An analog NAMUR high or low level is detected (AI only).
DEV_MALFUNC is True and not ignored via the HART_ERRORS parameter.
PV_FIXED is True and not ignored via the HART_ERRORS parameter.
There has been a problem configuring the HART instrument during initialization.
If any of the conditions below exist, OINTEG will be True (1) except for Good and Good - No Installed Config.