Series 2 redundant cards contain a microchip that enables redundancy. If the chip fails, the redundant cards stop communicating, and a switchover occurs instantaneously. To correct this issue:
Replace the faulty card.
Open DeltaV Diagnostics (click ).
For each card, right-click the card, and then select Clear Saved Fault Information.