Locks are also assigned to various SIS functions, such as downloading, uploading, changing the configuration database, and so on. Functions are assigned default locks initially. In DeltaV Explorer, use the Modify button on the Properties dialog for SIS Function Security to change the lock associated with an SIS function.
|
Function Name |
Default Associated Lock |
Function operation |
|---|---|---|
|
SIS_ALARM_HELP_DOWNLOAD |
SIS Can Download |
Download SIS alarm help to the DeltaV run-time system from the Alarm Help View and Edit application. |
|
SIS_ALARM_HELP_EDIT_COI |
SIS Can Configure |
Modify the Consequence of Inaction field in the Alarm Help View and Edit application. |
|
SIS_ALARM_HELP_EDIT_TTR |
SIS Can Configure |
Modify the Time to Respond field in the Alarm Help View and Edit application. |
|
SIS_ALARM_HELP_EDIT_TEXT1 |
SIS Can Configure |
Modify the upper text box in the Alarm Help View and Edit application. |
|
SIS_ALARM_HELP_EDIT_TEXT2 |
SIS Can Configure |
Modify the middle text box in the Alarm Help View and Edit application. |
|
SIS_ALARM_HELP_EDIT_TEXT3 |
SIS Can Configure |
Modify the lower text box in the Alarm Help View and Edit application. |
|
SIS_APPROVAL_01 through SIS_APPROVAL_05 |
SIS User Lock 06 through SIS User Lock 10 |
Approve SIS module authorization and functional test recording. |
|
SIS_CHANGE_CONFIG_DB |
SIS Can Configure |
Make changes to SIS objects in the configuration database, debug an SIS module. |
|
SIS_CHANGE_DEVICE_DB |
SIS Can Calibrate |
Use AMS Device Manager device configuration and calibration features. |
|
SIS_DIAGNOSTIC_DATA_CLEAR |
SIS Diagnostic |
Clear all communication, port, and device statistics; clear integrity history. |
|
SIS_DIAGNOSTIC_RESET |
SIS Diagnostic |
Reset (restart) the Logic Solver. |
|
SIS_DIAGNOSTIC_SWITCHOVER |
SIS Diagnostic |
Initiate a Logic Solver switchover. |
|
SIS_DOWNLOAD_CONFIG |
SIS Can Download |
Download configuration to the Logic Solver. |
|
SIS_EDIT_DOWNLOAD_MODULES |
SIS Can Edit |
Permits the following actions for SIS modules assigned to the
SIS nodes that have the SIS Can Edit key:
This key is node-specific. You can assign this key to a specific node or assign it to all nodes (sitewide). |
|
SIS_EDIT_IO_AND_SETUP_DEVICES |
SIS Can Setup Devices |
Permits the following functions for IO assigned to the nodes
that have the SIS Can Setup Devices lock:
This key is node-specific. You can assign this key to a specific node or assign it to all nodes (sitewide). In order for the logged in DeltaV user to be able to edit or set up I/O and devices, the I/O and devices must be assigned to a node to which this key is assigned. |
|
SIS_LOCK_LOGIC_SOLVER |
SIS Can Download |
Lock and unlock the Logic Solver. |
|
SIS_LOCK_UNLOCK_DEVICE |
SIS Can Calibrate |
Lock and unlock HART devices from Diagnostics. |
|
SIS_UPLOAD_CONFIG |
SIS Can Configure |
Upload online configuration changes to the SIS module configuration for a Logic Solver. |
|
SIS_USER_SECURITY_ATTACH_LOCKS |
SIS Can Configure |
Attach locks to SIS functions in DeltaV Explorer. |
|
SIS_VC_CHECKOUT_CHECKIN |
SIS Can Configure |
Check SIS objects in and out of Version Control database. |
|
SIS_VC_DOWNLOAD_CHECKEDOUT |
SIS Version Control |
Download SIS objects checked out of Version Control database. |
|
SIS_VC_DOWNLOAD_UNAUTHORIZED |
SIS Version Control |
Download SIS modules that are not authorized. |
|
SIS_VC_PURGE_RECOVER_ITEMS |
SIS Version Control |
Purge and recover SIS objects from the Version Control database. |
|
SIS_VC_ROLLBACK_ITEMS |
SIS Version Control |
Rollback to a previous version of an SIS object. |