This section lists the effect of HART error conditions on DeltaV Diagnostic parameters. For ease of use the information is organized into two tables. This table lists the status returned to the following Diagnostics parameters as a result of HART error conditions:
The following table lists the status returned to OINTEG, NPV_PAST_LIM, PV_FIXED,PV_PAST_LIM,PV_SAT
HART Error Condition |
Status returned to: |
|||||
|---|---|---|---|---|---|---|
COLD_START |
CONFIG_CHANGED |
DEV_CFG_MISMATCH |
DEV_MALFUNC |
HINTEG |
MORE_STATUS |
|
Channel Type |
AI, AO |
AI, AO |
AI, AO |
AI, AO |
AI, AO |
AI, AO |
Controller Configuration Error |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
I/O card A/D error |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
I/O card open loop |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
I/O card loss of digital comms |
No effect |
No effect |
No effect |
No effect |
TRUE(1) |
No effect |
PV not reported by device |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
DV not configured in controller |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
DV not reported by device |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Diagnostics in progress |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
High, low, or high high alarm |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Scale error and no comm |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Scale error and good comm |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Device malfunction |
No effect |
No effect |
No effect |
TRUE |
TRUE |
No effect |
Device configuration changed |
No effect |
TRUE |
No effect |
No effect |
No effect |
No effect |
Device cold start |
TRUE |
No effect |
No effect |
No effect |
No effect |
No effect |
Device more status available |
No effect |
No effect |
No effect |
No effect |
No effect |
TRUE |
Device analog output current fixed |
No effect |
No effect |
No effect |
No effect |
TRUE |
No effect |
Device analog output saturated |
No effect |
No effect |
No effect |
No effect |
TRUE |
No effect |
Device primary variable out of limits |
No effect |
No effect |
No effect |
No effect |
TRUE |
No effect |
Device non-primary variable out of limits |
No effect |
No effect |
No effect |
No effect |
TRUE |
No effect |
Device alerts enabled and device ID mismatch |
No effect |
No effect |
TRUE |
No effect |
No effect |
No effect |
Stale data |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
HART busy, HART update warning, 5% comm error |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
This table lists the status returned to the following Diagnostics parameters as a result of HART error conditions:
HART Error Condition |
Status returned to: |
||||||
|---|---|---|---|---|---|---|---|
NO_COMM |
OINTEG |
OINTEG |
NPV_PAST_LIM |
PV_FIXED |
PV_PAST_LIM |
PV_SAT |
|
Channel Type |
AI, AO |
AI |
AO |
AI, AO |
AI, AO |
AI, AO |
AI, AO |
Controller Configuration Error |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
I/O card A/D error |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
I/O card open loop |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
I/O card loss of digital comms |
TRUE |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
PV not reported by device |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
DV not configured in controller |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
DV not reported by device |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Diagnostics in progress |
No effect |
No effect |
BAD |
No effect |
No effect |
No effect |
No effect |
High, low, or high high alarm |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
Scale error and no comm |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
Scale error and good comm |
No effect |
BAD |
BAD |
No effect |
No effect |
No effect |
No effect |
Device malfunction |
No effect |
BAD(1) |
BAD(1) |
No effect |
No effect |
No effect |
No effect |
Device configuration changed |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Device cold start |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Device more status available |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Device analog output current fixed |
No effect |
BAD(1) |
BAD(1) |
No effect |
TRUE |
No effect |
No effect |
Device analog output saturated |
No effect |
BAD(1) |
BAD(1) |
No effect |
No effect |
No effect |
TRUE |
Device primary variable out of limits |
No effect |
BAD(1) |
BAD(1) |
No effect |
No effect |
TRUE |
No effect |
Device non-primary variable out of limits |
No effect |
No effect |
No effect |
TRUE |
No effect |
No effect |
No effect |
Device alerts enabled and device ID mismatch |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
Stale data |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
HART busy, HART update warning, 5% comm error |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |
No effect |