HART devices and the DeltaV System > HART error conditions for Classic I/O

Effect of HART error conditions on diagnostic status text (Classic I/O)

Error conditions trigger status information in DeltaV Diagnostics to help you troubleshoot problems The following table lists the error conditions and the diagnostic status information that results from the error.

Table: Diagnostic Status Information Resulting from HART Error Conditions (Classic I/O)

HART Error

Diagnostics Status Information

Description

PIO Channel Status - Config Error, Config Not Usable, Config Not Current

Bad - Configuration Error

The channel encountered an error while configuring the channel.

PIO Channel Status - Config Error, Config Not Usable, Config Not Current

A/D Converter Error

The HART channel detected an error in its A/D converter (AI only).

Channel Status - AI Low Alarm

Open Loop Detected

The HART channel has detected an open loop.

Channel Status - AO Open Loop

Open Loop Detected

The HART channel has detected an open loop.

Channel Status - AI High Alarm

Short Circuit Detected

The HART channel has detected a short circuit.

Channel Status - AI Low Low Alarm

Namur Low Limit Detected

Channel Status - AI High High Alarm

Namur High Limit Detected

Channel Status - AO Diagnostics in Progress

Diagnostics in Progress

The HART channel is performing Valve Diagnostics (Valve Stimulus Testing) on a Fisher Controls valve (AOUT only).

Device - Scale Not Valid && Scaling Not in Progress && Channel Status - HART No Comm

Not Communicating With Device

The HART channel is unable to digitally communicate with the attached HART instrument.

Device - Scale Not Valid && Scaling Not in Progress && Channel Status - HART No Comm

Unable To Identify Device - Unsupported HART Revision

Device - Scale Not Valid && Scaling Not in Progress && Device ID Not Valid && Command 0 Command Status is BUSY

Unable To Identify Device - Device Is Busy

Device - Scale Not Valid && Scaling Not in Progress && Device ID Not Valid && Command 0 Command Status is ACCESS RESTRICTED

Unable To Identify Device - Access Restricted

Device - Scale Not Valid && Scaling Not in Progress && Device ID Not Valid && Command 0 Command Status is DEVICE SPECIFIC ERROR

Unable To Identify Device - Device Error

Device - Scale Not Valid && Scaling Not in Progress && Device ID Not Valid && Command 0 Command Status is not NO ERRORS

Unable To Identify Device

Device - Scale Not Valid && Scaling Not in Progress && Command 15 Command Status is BUSY

Device Configuration Cannot Be Read - Device Is Busy

The HART channel attempted to read the analog output scale information of the attached HART instrument, and the instrument reported a problem.

Device - Scale Not Valid && Scaling Not in Progress && Command 15 Command Status is ACCESS RESTRICTED

Device Configuration Cannot Be Read - Access Restricted

The HART channel attempted to write the analog output scale information to the attached HART instrument, and the instrument reported that it has restricted access.

Device - Scale Not Valid && Scaling Not in Progress && Command 15 Command Status is DEVICE SPECIFIC ERROR

Device Configuration Cannot Be Read - Device Error

Device - Scale Not Valid && Scaling Not in Progress && Command 15 Command Status is !NO ERRORS

Device Configuration Cannot Be Read

The HART channel attempted to read the analog output scale information of the attached HART instrument, and the instrument reported a problem.

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is INVALID SELECTION

Device Range Invalid

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is UPPER RANGE TOO HIGH

Device Range Upper Value Too High

The HART channel attempted to configure the analog output scale information of the attached HART instrument, and the instrument reported that upper range value was too high.

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is UPPER RANGE TOO LOW

Device Range Upper Value Too Low

The HART channel attempted to configure the analog output scale information of the attached HART instrument, and the instrument reported that the upper range value was too low.

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is LOWER RANGE TOO HIGH

Device Range Lower Value Too High

The HART channel attempted to configure the analog output scale information of the attached HART instrument, and the instrument reported that the lower range value was too high.

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is LOWER RANGE TOO LOW

Device Range Lower Value Too Low

The HART channel attempted to configure the analog output scale information of the attached HART instrument, and the instrument reported that the lower range value was too low.

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is BOTH RANGE ERROR

Device Range Values Out Of Limits

The HART channel attempted to configure the analog output scale information of the attached HART instrument, and the instrument reported that upper range value was too high.

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is BUSY

Device Range Cannot Be Changed - Device Is Busy

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is WRITE PROTECTED

Device Range Cannot Be Changed - Write Protected

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is ACCESS RESTRICTED

Device Range Cannot Be Changed - Access Restricted

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is INCORRECT_INSTRUMENT_MODE

Device Range Cannot Be Changed - Device Error

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is INVALID_UNITS

Device Range Units Invalid

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is INVALID_SPAN

Device Range Span Invalid

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is TOO FEW DATA BYTES IN REQ

Device Range Invalid

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is DEVICE SPECIFIC ERROR

Device Range Cannot Be Changed - Device Error

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is COMMAND NOT SUPPOERED

Device Range Cannot Be Changed - Command Not Supported

Device - Scale Not Valid && Scaling Not in Progress && Command 35 Command Status is !SET_TO_NEAREST_VALUE && !SPAN_TOO_SMALL && !NO_ERRORS

Device Range Cannot Be Changed

Device - Scale Not Valid && Scaling Not in Progress && Command 44 Command Status is INVALID SELECTION

Device Units invalid

Device - Scale Not Valid && Scaling Not in Progress && Command 44 Command Status is BUSY

Device Units Cannot Be Changed - Device Is Busy

Device - Scale Not Valid && Scaling Not in Progress && Command 4 Command Status is WRITE PROTECTED

Device Units Cannot Be Changed - Write Protected

Device - Scale Not Valid && Scaling Not in Progress && Command 44 Command Status is ACCESS RESTRICTED

Device Units Cannot Be Changed - Access Restricted

Device - Scale Not Valid && Scaling Not in Progress && Command 44 Command Status is TOO FEW DATA BYTES IN REQ

Device Units Invalid

Device - Scale Not Valid && Scaling Not in Progress && Command 44 Command Status is DEVICE SPECIFIC ERROR

Device Units Cannot Be Changed - Device Error

Device - Scale Not Valid && Scaling Not in Progress && Command 44 Command Status is COMMAND NOT SUPPORTED

Device Units Cannot Be Changed - Command Not Supported

Device - Scale Not Valid && Scaling Not in Progress && Command 38 Command Status is BUSY

Cannot Clear Device Change Flag - Device Is busy

Device - Scale Not Valid && Scaling Not in Progress && Command 38 Command Status is WRITE_PROTECTED

Cannot Clear Device Change Flag - Write Protected

Device - Scale Not Valid && Scaling Not in Progress && Command 38 Command Status is ACCESS RESTRICTED

Cannot Clear Device Change Flag - Access Restricted

Device - Scale Not Valid && Scaling Not in Progress && Command 38 Command Status is DEVICE SPECIFIC ERROR

Cannot Clear Device Change Flag - Device Error

Device - Scale Not Valid && Scaling Not in Progress && Command 38 Command Status is COMMAND NOT SUPPORTED

Cannot Clear Device Change Flag - Command Not Supported

Device - Scale Not Valid && Scaling Not in Progress && Command 38 Command Status is !NO ERRORS

Cannot Clear Device Change Flag

Device - Scale Not Valid && Scaling Not in Progress

Configuration Scale Does Not Match Device

Field Device Status - Field Device Malfunction (and not overridden)

Device Malfunction

The HART instrument detected a problem with itself or with one of its associated sensors.

Field Device Status - Loop Current Fixed (and not overridden)

Loop Current Fixed

Field Device Status - Loop Current Saturated (and not overridden

Loop Current is Saturated

Field Device Status - Primary Variable Out of Limits (and not overridden)

Primary Variable Out of Limits

The HART instrument is reporting that the primary measurement is outside the sensor limits.

Channel Status - HART No Comm

Not Communicating With Device

The HART channel is unable to digitally communicate with the attached HART instrument.

Primary Variable not reported

Primary Variable Not Reported

Device Variable configured but not reported

Device Variable Configured But Not Reported

Field Device Status - Non-Primary Variable Out of Limits (and not overridden)

Non-Primary Variable Out of Limits

The HART instrument is reporting that one of the non-primary measurements is outside the associated sensor limits.

PIO Channel Status - Stale Data

Stale Data

HART Data Poll Command Status is BUSY

Stale HART Data

HART Data Poll Command Status is UPDATE FAILURE

Stale HART Data

Device - Command 48 Command Status is BUSY

Cannot Read Device Alerts - Device Is busy

Device - Command 48 Command Status is ACCESS RESTRICTED

Cannot Read Device Alerts - Access Restricted

Device - Command 48 Command Status is DEVICE ERROR

Cannot Read Device Alerts - Device Error

Device - Command 48 Command Status is UPDATE IN PROGRESS

Cannot Read Device Alerts - Update In Progress

Device - Command 48 Command Status is COMMAND NOT SUPPORTED

Cannot Read Device Alerts - Command Not Supported

Device - Command 48 Command Status is not NO ERRORS

Cannot Read Device Alerts

Device - Alerts Enabled && !Valid

Device Alerts Not Reported

Device - Command 132 Command Status is BUSY

Cannot Read Device Diagnostics Data - Device Is busy

Device - Command 132 Command Status is ACCESS RESTRICTED

Cannot Read Device Diagnostics Data - Access Restricted

Device - Command 132 Command Status is DATA NOT AVAILABLE

Cannot Read Device Diagnostics Data - Data Not Available

Device - Command 132 Command Status is DATA NOT READY

Cannot Read Device Diagnostics Data - Data Not Ready

Device - Command 132 Command Status is COMMAND NOT SUPPORTED

Cannot Read device Diagnostics Data - Command Not Supported

Device - Command 132 Command Status is not NO ERRORS

Cannot Read Device Diagnostics Data

Channel Status - HART 5% Comm Error

5% Comm Error Rate with Device

Field Device Status - Field Device Malfunction (and overridden)

Device Malfunction

Field Device Status - Cold Start

Device has been Reset

Field Device Status - Loop Current Fixed (and overridden)

Loop Current Fixed

Field Device Status - Loop Current Saturated (and overridden)

Loop Current is Saturated

Field Device Status - Primary Variable Out of Limits (and overridden)

Primary Variable Out of Limits

Field Device Status - Non-Primary Variable Out of Limits (and overridden)

Non-Primary Variable Out of Limits

Field Device Status - More Status Available

Device Alert

Device - Command 35 Command Status is SPAN TOO SMALL

Device Range Span Too Small

Device - Command 35 Command Status is SET TO NEAREST VALUE

Device Range Set to Nearest Possible Value

No Error

Good