Tables A and B below list the values expected for diagnostic parameters when the following HART communication and mismatch error conditions are detected by DeltaV Diagnostics:
HART server error
HART communication error
Device revision mismatch
Loop current mismatch
Scale mismatch
Diagnostics in progress
Non-Primary Variable out of limits
Stale
| Parameter | HART server error(1) | HART communication error | Device revision mismatch | Loop current mismatch |
|---|---|---|---|---|
OINTEG |
BAD |
BAD |
— |
|
HINTEG |
— |
TRUE |
— |
— |
NO_COMM |
— |
TRUE |
— |
— |
DEV_CFG_MISMATCH |
— |
— |
TRUE(3) |
|
DISPARITY_DETECT |
— |
— |
— |
|
HART_FIELD_VAL(4) |
— |
— |
— |
|
HART_PV |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_SV |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_TV |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_FV |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_DV_SLOT0(5) |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_DV_SLOT1(5) |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_DV_SLOT2(5) |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
HART_DV_SLOT3(5) |
BadNoCommLUV |
BadNoCommLUV |
— |
— |
| Parameter | Scale mismatch | Diagnostics in progress | Update Warning, Busy, Access Restricted, Delayed Response |
|---|---|---|---|
OINTEG (HART integrity) |
BAD |
BAD |
— |
HINTEG |
— |
— |
— |
NO_COMM |
— |
— |
— |
DEV_CFG_MISMATCH |
— |
— |
— |
DISPARITY_DETECT |
— |
— |
— |
HART_FIELD_VAL(4) |
BadConfigError |
BadOutOfService |
|
HART_PV |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_SV |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_TV |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_FV |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_DV_SLOT0(5) |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_DV_SLOT1(5) |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_DV_SLOT2(5) |
— |
BadOutOfService |
UncertainNonSpecific(1) |
HART_DV_SLOT3(5) |
— |
BadOutOfService |
UncertainNonSpecific(3) |