HART devices and the DeltaV System > HART error conditions for CHARMs I/O

HART command errors (CHARMs I/O)

This table lists the values expected for diagnostic parameters when the following HART command errors are detected by DeltaV Diagnostics:

  • Command 3 error

  • Command 9 error

  • Command 33 error

  • Nonzero varable status

  • Unconfigured

  • Unsupported

Parameter Command 3 error Command 9 error Command 33 error Non-zero variable status Unconfigured Unsupported

OINTEG

(HART integrity)

BAD

BAD

BAD

BAD(1)(2)(3)

BAD(2)

DEV_CFG_MISMATCH

DISPARITY_DETECT

True(3)(4)

HART_FIELD_VAL(5)

HART_PV

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

HART_SV

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

HART_TV

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

HART_FV

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

HART_DV_SLOT0(6)

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

BadConfigError(2)

HART_DV_SLOT1(6)

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

BadConfigError(2)

HART_DV_SLOT2(6)

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

BadConfigError(2)

HART_DV_SLOT3(6)

BadNonSpecific

BadNonSpecific

BadNonSpecific(1)(3)

BadConfigError(2)

BadConfigError(2)

(1) Any time configured variables have a nonzero status in response to Command 9, only the status of those variables is set to BAD.
(2) Any time a dynamic or device variable is not reported by the device or is not configured, the status of those variables is set to BAD. If PV is BAD, OINTEG is also set to BAD.
(3) Unless ignored by configuration.
(4) Unless disabled by configuration.
(5) Any condition that causes the analog value FIELD_VAL_PCT to have bad integrity or status will also cause HART_FIELD_VAL to have bad integrity and status.
(6) This channel parameter is not supported in devices implementing the HART Protocol prior to revision 7. Therefore, any HART command error appearing in DeltaV Diagnostics for a device that implements an earlier level of the HART protocol can be disregarded.