The following tables list the VCR specifications for certain fieldbus devices. The tables are organized according to whether the devices use Free VCRs or not.
The following table shows the maximum number of free VCRs for those devices supported by the DeltaV system that use Free VCRs. Each port on the H1 card supports a maximum of 50 linkable VCRs (a maximum of 50 device subscribers or 35 H1 publishers). Enabling fieldbus alarms in a device consumes one alarm VCR and reduces by one the available number of Free VCRs for publisher and subscriber links.
| Device | Revision | Max number free VCRs | Link master capable |
|---|---|---|---|
ASCO Controls 4449 |
1 |
6 |
Y |
CSI 9210 Machinery Health Transmitter |
2 |
8 |
Y |
El-O-Matic 0990 ELQ On/Off Extended |
3 |
8 |
N |
4 |
9 |
Y |
|
El-O-Matic 22C0 ELQ On/Off Advanced |
3 |
9 |
N |
4 |
9 |
Y |
|
El-O-Matic 7360 ELQ Positioner Extended |
3 |
9 |
N |
4 |
6 |
Y |
|
El-O-Matic 8000 ELQ Positioner Basic |
3 |
8 |
N |
4 |
5 |
Y |
|
El-O-Matic A2C0 ELQ On/Off Pneumatic |
4 |
8 |
N |
El-O-Matic DD30 ELQ Positioner Advanced |
3 |
8 |
N |
4 |
7 |
Y |
|
El-O-Matic F800 ELQ On/Off Basic |
3 |
8 |
N |
4 |
5 |
Y |
|
Fisher-Rosemount Systems DeltaV H1 Carrier |
1 |
9 |
N |
2 |
9 |
Y |
|
Fisher Controls DVC5000f fieldbus Digital Valve Controller (300) |
6 |
10 |
N |
Fisher Controls DVC5000f AO/PID Digital Valve Controller (5400) |
7 |
12 |
N |
Fisher Controls DVC5000f AO/PID/IS Digital Valve Controller (5420) |
8 |
16 |
N |
9 |
16 |
N |
|
Fisher Controls DVC5000f DO/DI Digital Valve Controller |
7 |
11 |
N |
8 |
8 |
N |
|
Fisher Controls DVC6000f - SC rev 1 |
1 |
17 |
N |
Micro Motion 2000 (2700 Coriolis Flow Meter) |
1 |
4 |
N |
2 |
5 |
Y |
|
3 |
14 |
Y |
|
4 |
20 |
Y |
|
Micro Motion 5300 (Coriolis Flow Meter) |
1 |
5 |
N |
Rosemount 644 fieldbus Temperature Transmitter |
1 |
9 |
N |
Rosemount 848 fieldbus Temperature Device |
4 |
16 |
Y |
5 |
16 |
Y |
|
Rosemount 848L Logic fieldbus Transmitter |
1 |
16 |
Y |
Rosemount 752 fieldbus Remote Display |
2 |
17 |
Y |
Rosemount 3244MV fieldbus Temperature Transmitter |
2 |
6 |
N |
3 |
9 (this revision supports a maximum of 5 subscriber VCRs) |
Y |
|
4 |
9 |
Y |
|
Rosemount 3051 fieldbus Pressure Transmitter |
3 |
6 |
N |
6 |
8 |
Y |
|
7 |
9 |
Y |
|
20 |
16 |
Y |
|
23 |
17 |
Y |
|
Rosemount 3144 fieldbus Temperature Transmitter |
1 |
17 |
Y |
Rosemount 3900 TankRadar REX Level Transmitter |
1 |
14 |
Y |
Rosemount 5600 TankRadar PRO Level Transmitter |
1 |
7 |
Y |
Rosemount 8742 Magnetic Flow |
1 |
6 |
N |
3 |
8 |
N |
|
4 |
9 |
N |
|
5 |
16 |
Y |
|
Rosemount 8800 fieldbus Vortex Flow Transmitter |
1 |
6 |
N |
2 |
5 |
N |
|
3 |
6 |
Y |
|
4 |
8 |
Y |
|
5 |
8 |
Y |
|
Rosemount Analytical 1000 Continuous Gas Analyzer |
3 |
9 |
Y |
Rosemount Analytical 1100 MLT Continuous Gas Analyzer |
1 |
16 |
Y |
Rosemount Analytical 4081 pH fieldbus Transmitter |
1 |
5 |
N |
2 |
7 |
Y |
|
3 |
8 |
Y |
|
Rosemount Analytical 4081 C/T fieldbus Transmitter |
1 |
6 |
N |
2 |
8 |
Y |
|
Rosemount Analytical 4081 Flue Gas |
1 |
6 |
N |
2 |
7 |
Y |
|
Rosemount Analytical OXT 5000 |
1 |
6 |
N |
3 |
8 |
Y |
|
Rosemount Analytical 1000 Continuous Gas Analyzer |
3 |
9 |
Y |
Rosemount Analytical 5081 pH fieldbus Transmitter |
1 |
8 |
Y |
Rosemount Analytical 5081A fieldbus Transmitter (Amperometric) |
1 |
7 |
Y |
Rosemount Analytical 5081C/T fieldbus Transmitter |
1 |
8 |
Y |
Rosemount Analytical Xmt-A-FF |
1 |
19 |
Y |
Rosemount Analytical Xmt-C/T-FF |
1 |
19 |
Y |
Rosemount Analytical Xmt-P-FF |
1 |
19 |
Y |
Valve Automation D3A0 FieldQ Pneumatic Valve Actuator |
1 |
8 |
Y |
2 |
15 |
N |
|
ABB Pressure Transmitter (600T) |
1 |
3 |
N |
2 |
11 |
Y |
|
ABB 2000T Pressure Transmitter Rev 1 |
1 |
3 |
N |
ABB 2000T/2600T (263/265) Pressure Series |
2 |
11 |
N |
ABB 2600T (262/264) Pressure Series |
1 |
11 |
Y |
2 |
25 |
Y |
|
ABB 2600T (267/269) Pressure Series Rev 2 |
2 |
12 |
N |
ABB TRIO-WIRL Flow Meter |
1 |
2 |
Y |
ABB FXE4000 Magmeter Series |
2 |
12 |
Y |
ABB FSM4000 Magmeter Series |
1 |
12 |
N |
ABB pH/ORP/pION Transmitter (TB82pH) |
1 |
2 |
N |
ABB TB82TE Conductivity, Concentration Transmitter (2- Electrode) |
1 |
2 |
N |
ABB TB82EC Conductivity, Concentration Transmitter (4-Electrode) |
1 |
2 |
N |
ABB Temperature Transmitter (TF02, TF102, TF202) |
1 |
3 |
N |
ABB TZID-C120 |
2 |
12 |
N |
Anderson Instruments Pressure TB-Interface |
1 |
2 |
N |
Anderson Instruments Temperature TB-Interface |
1 |
2 |
N |
AUMA Aumatic FF H1 |
1 |
21 |
Y |
BEKA associates Ltd. fieldbus Display |
2 |
21 |
N |
BEKA associates Ltd. fieldbus Indicator |
1 |
12 |
N |
Biffi FF 2000 v4 |
1 |
25 |
N |
Berthold Technologies Uni-Probe LB490 |
2 |
3 |
Y |
Berthold Technologies Uni-Probe LB491 |
2 |
12 |
Y |
Buerkert Werke Power I/O Box |
1 |
12 |
N |
Dresser FVP Valve Positioner |
4 |
20 |
Y |
Dresser FVP (software download) |
2 |
20 |
Y |
Dynamic Flow Computers |
1 |
6 |
Y |
EIM Controls EA00 Positioner |
1 |
8 |
Y |
EIM Controls ED00 fieldbus OnOffValve |
1 |
8 |
Y |
Endress+Hauser CERABAR S |
1 |
2 |
N |
2 |
12 |
N |
|
Endress+Hauser DELTABAR S |
1 |
3 |
N |
2 |
12 |
N |
|
Endress+Hauser Gammapilot M |
1 |
21 |
Y |
Endress+Hauser MICROPILOT II |
1 |
3 |
N |
Endress+Hauser Micropilot M |
2 |
11 |
N |
3 |
11 |
Y |
|
4 |
21 |
Y |
|
5 |
21 |
Y |
|
Endress+Hauser Promass 83 |
1 |
14 |
Y |
2 |
20 |
Y |
|
3 |
25 |
Y |
|
Endress+Hauser DELTAPILOT S |
1 |
11 |
N |
Endress+Hauser LEVELFLEX M |
3 |
11 |
Y |
21 |
Y |
Y |
|
Endress+Hauser Liquiline M CM 42 Cond |
1 |
6 |
Y |
Endress+Hauser Liquiline M CM 42 pH/ORP |
1 |
6 |
Y |
Endress+Hauser Promag 53 |
1 |
10 |
N |
2 |
17 |
N |
|
3 |
25 |
Y |
|
Endress+Hauser Prosonic Flow 92 |
1 |
24 |
Y |
Endress+Hauser Prosonic 93 |
1 |
20 |
Y |
2 |
20 |
Y |
|
Endress+Hauser PROSONIC M |
3 |
11 |
Y |
4 |
21 |
Y |
|
Endress+Hauser Prowirl 72 |
1 |
4 |
Y |
Endress+Hauser Prowirl 73 |
1 |
11 |
Y |
Endress+Hauser RID1X |
1 |
24 |
Y |
Foxboro-Eckardt RTT15-F |
1 |
11 |
Y |
FlowServe AccuMX Application |
2 |
15 |
Y |
FlowServe Valve Controller |
4 |
12 |
N |
5 |
12 |
N |
|
Fuji Electric FCX-A2 Pressure Transmitter |
1 |
1 |
N |
Heinrichs Messtechnik |
1 |
11 |
N |
Honeywell Pressure Transmitter (ST3000FF) |
6 |
10 |
N |
7 |
11 |
N |
|
8 |
10 |
N |
|
Honeywell Temperature Transmitter (STT35F) |
2 |
10 |
N |
Invensys Process Systems (Foxboro) IASPT10 |
22 |
3 |
N |
32 |
11 |
N |
|
Invensys Process Systems (Foxboro) SRD960 Valve Positioner |
9 |
12 |
Y |
Invensys Process Systems (Foxboro) SRD991 Valve Positioner |
9 |
12 |
Y |
16 |
17 |
Y |
|
Knick Elektronische Messgerate Stratos FF 2231X Oxy |
1 |
4 |
N |
Knick Elektronische Messgerate Stratos FF 2231X pH |
1 |
4 |
N |
Knick Elektronische Messgerate Stratos FF 2232X CondI |
1 |
4 |
N |
KOSO America REXA XPAC Actuator |
1 |
10 |
N |
KROHNE BM 70 A/P Radar Level Meter |
2 |
5 |
N |
3 |
5 |
N |
|
KROHNE IFC090 Compact Electromagnetic Flowmeter |
1 |
13 |
N |
KTEK AT100 |
1 |
24 |
Y |
Limitorque MX100 |
1 |
15 |
N |
LEDEEN LFFC-LD-1.0 |
1 |
17 |
N |
Magnetrol, Model 705 3.x |
1 |
5 |
Y |
2 |
13 |
Y |
|
Magnetrol, Orion Jupiter Model 2xx |
1 |
3 |
Y |
MagTech LTM-300 |
1 |
4 |
N |
METTLER-TOLEDO Oxy 4100 FF |
1 |
4 |
N |
METTLER-TOLEDO pH 2100 FF |
1 |
4 |
N |
METTLER-TOLEDO Cond Ind 7100e FF |
1 |
4 |
N |
METTLER-TOLEDO M700 FF700 |
1 |
13 |
N |
Metso Automation NELES Valve-1 Positioner |
3 |
12 |
Y |
Metso Automation ND9000F Valve Controller (Rev 1) |
1 |
17 |
Y |
Metso Automation ND9000F Valve Controller (Rev 2) |
2 |
17 |
N |
Metso Automation ND9000F Valve Controller (Rev 3) |
3 |
21 |
N |
MTL F809F |
1 |
11 |
N |
Ohmart fieldbus Level/Density |
2 |
6 |
N |
OVAL Corporation EX-DELTA (Vortex Flowmeter) |
1 |
2 |
N |
Pepperl+Fuchs RDO-TI-Ex8-FF |
1 |
17 |
N |
Pepperl+Fuchs FDO-VC-Ex4.FF |
1 |
21 |
N |
2 |
14 |
N |
|
PR Electronics PRetop 5350 FF (Head Mount Temperature Transmitter) |
2 |
11 |
Y |
PR Electronics PRetrans 6350 (Panel Mount Temperature Transmitter) |
1 |
11 |
Y |
Rotork, ROTORK ACTUATOR |
1 |
17 |
N |
SAMSON AG Advanced Positioner Type 3787 |
1 |
10 |
N |
2 |
14 |
Y |
|
SAMSON AG Positioner 373x5 |
1 |
14 |
N |
Siemens AG Positioner SIPART PS2 FF |
1 |
12 |
N |
2 |
12 |
N |
|
StoneL Corporation FF VCT |
1 |
9 |
N |
2 |
9 |
N |
|
StoneL Corporation FF I/O Module 52 |
1 |
9 |
N |
2 |
9 |
N |
|
StoneL Corporation FF I/O Module F2 |
1 |
13 |
N |
2 |
13 |
N |
|
TopWorx DVC-FF Discrete Valve Controller |
2 |
16 |
N |
VEGA Grieshaber VEGABAR (Pressure Transmitter) |
1 |
4 |
N |
3 |
4 |
Y |
|
VEGA Grieshaber VEGACAL |
1 |
3 |
Y |
3 |
3 |
Y |
|
VEGA Grieshaber VEGA FLEX (Guided Microwave Transmitter) |
1 |
3 |
N |
3 |
3 |
Y |
|
VEGA Grieshaber VEGA PULS (Radar Level Transmitter) |
1 |
3 |
N |
3 |
3 |
Y |
|
Vega Grieshaber VEGASON (Ultrasonic Level Transmitter) |
1 |
4 |
N |
3 |
4 |
Y |
|
Yamatake Corporation ATT (Temperature Transmitter) |
1 |
13 |
N |
Yamatake Corporation Standard Magnetic Flow Transmitter |
2 |
2 |
N |
Yamatake Corporation DST (Pressure Transmitter) |
1 |
11 |
N |
Yamatake Corporation AVP (Valve Positioner) |
1 |
13 |
N |
2 |
13 |
N |
|
Yokogawa Electric, AV550G |
1 |
14 |
Y |
Yokogawa Electric, AXF |
1 |
25 |
Y |
Yokogawa Electric, DO202-F Dissolved Oxygen Transmitter |
3 |
4 |
Y |
Yokogawa Electric DYF/LC1 (Vortex Flowmeter) |
1 |
13 |
Y |
Yokogawa Electric EJA100A (Pressure Transmitter) |
1 |
4 |
N |
2 |
11 |
Y |
|
Yokogawa Electric EJX |
3 |
25 |
Y |
Yokogawa Electric YVP Valve Positioner |
2 |
12 |
N |
3 |
20 |
Y |
|
4 |
20 |
Y |
|
Yokogawa Electric YVP Valve Positioner (software download) |
2 |
20 |
Y |
Yokogawa Electric AE100 (Mag Flowmeter) |
1 |
9 |
Y |
Yokogawa Electric YTA320 (Temperature Transmitter) |
2 |
25 |
Y |
Yokogawa Electric DAQSTATION |
3 |
17 |
Y |
Yokogawa Electric YF100 (YEWFLOW) Vortex Flowmeter |
1 |
2 |
N |
2 |
10 |
N |
|
Yokogawa Electric, YPK (Software Download) |
1 |
20 |
Y |
Yokogawa Electric, YVP (Software Download) |
1 |
20 |
Y |
Yokogawa Electric PH202-F (pH Analyzer) |
1 |
4 |
N |
2 |
4 |
N |
|
3 |
4 |
Y |
|
Yokogawa Electric SC202-F (Conductivity/Resistivity Analyzer) |
1 |
4 |
N |
2 |
4 |
N |
|
3 |
4 |
Y |
|
Yokogawa Electric ISC202-F (Inductivity/Conductivity Analyzer) |
1 |
4 |
N |
2 |
4 |
N |
|
3 |
4 |
Y |
|
Yokogawa Electric ROTAMASS |
1 |
25 |
Y |
Yokogawa Electric ROTAMASS |
2 |
25 |
N |
Westlock BIFFIICON2000 |
1 |
17 |
N |
Westlock FPAC Valve Controller EL40106 |
1 |
17 |
N |
The following table shows the maximum number of Publisher and Subscriber VCRs for these generic devices supported by the DeltaV system. These devices do not support Free VCRs. Each port on the H1 card supports a maximum of 50 VCRs.
| Device | Revision | Max number publisher VCRs | Max number subscriber VCRs | Link master capable |
|---|---|---|---|---|
Dynisco Instrumnets FFX |
1 |
23 |
23 |
N |
Endress+Hauser Cerabar S |
5 |
11 |
12 |
Y |
Endress+Hauser Cerabar S |
6 |
12 |
12 |
Y |
Endress+Hauser Deltabar S |
5 |
12 |
12 |
Y |
Endress+Hauser Deltabar S |
6 |
12 |
12 |
Y |
Endress+Hauser Deltapilot S |
6 |
12 |
12 |
Y |
Endress+Hauser Liquiline M CM 42 Doxygen |
1 |
6 |
0 |
Y |
Endress+Hauser Prowirl 72 |
1 |
4 |
1 |
Y |
Endress+Hauser Prowirl 73 |
1 |
11 |
2 |
Y |
Endress+Hauser Temperature Transmitter TMT 85 |
1 |
7 |
12 |
Y |
Endress+Hauser Temperature Transmitter TMT 162 |
1 |
7 |
12 |
Y |
Endress+Hauser Temperature Transmitter TMT 165 |
4 |
4 |
6 |
N |
Flowserve Corporation BUSWITCH |
2 |
6 |
6 |
N |
3 |
6 |
2 |
N |
|
KTEK AT100 |
1 |
13 |
11 |
Y |
2 |
7 |
6 |
Y |
|
KTEK MT5000 |
1 |
6 |
6 |
Y |
Rotork ROTORK (IQ, AQ, Q, IQM, AQM Electric Actuator) |
1 |
9 |
9 |
N |
2 |
14 |
10 |
N |
|
SMAR Pressure Transmitter (LD302) |
2 |
6 |
6 |
N |
3 |
6 |
6 |
N |
|
4 |
3 |
6 |
Y |
|
SMAR Temperature Transmitter (TT302) |
2 |
6 |
6 |
N |
3 |
6 |
6 |
N |
|
4 |
4 |
6 |
Y |
|
SMAR Current Transmitter (IF302) |
2 |
6 |
6 |
N |
3 |
6 |
6 |
N |
|
4 |
5 |
6 |
Y |
|
SMAR Current Output Transmitter (FI302) |
2 |
6 |
6 |
N |
3 |
6 |
6 |
N |
|
4 |
8 |
9 |
Y |
|
SMAR Basic Positioner Transmitter (FP302) |
2 |
6 |
6 |
N |
3 |
6 |
6 |
N |
|
4 |
4 |
7 |
Y |
|
SMAR Advanced Positioner Transmitter (FY302) |
2 |
6 |
6 |
N |
3 |
6 |
6 |
N |
|
4 |
4 |
7 |
Y |