The DeltaV I/O network > What is a CIOC?
Upgrade redundant CIOCs
- Using the DeltaV Controller and I/O Upgrade Utility, upgrade the standby CIOC.
- Once the upgrade is complete, use DeltaV Diagnostics to monitor the standby CIOC OINTEG until it becomes GOOD (this can be 3 minutes on a fully loaded CIOC).
- Select the other CIOC in the redundant pair and start the upgrade.