The Operator Statistics module template (ALM_STATISTICS) is used to gather and compute statistics for active, shelved, stale and acknowledged alarms. The ALM_STATISTICS module requires some additional configuration in order to set it up; it is intended that the module will be configured by an experienced DeltaV control engineer familiar with Visual Basic and DeltaV Operate (Configure) schedules.
The ALM_STATISTICS module template includes the following parameters:
| Parameter | Description |
|---|---|
| ACK_ALM_AVG |
The calculated average of acknowledged alarms for last month which is computed in the CALC block. |
| ACK_ALM_SUM | Running total of ACK_ALMS computed every 1am and 1pm of each day of the month. ACK_ALM_SUM resets to 0 at the beginning of each month. |
| ACK_ALMS | Acknowledged alarms count |
| ACTIVE_ALM_AVG |
The calculated average of active alarms for last month which is computed in the CALC block. |
| ACTIVE_ALM_SUM | Running total of ACTIVE_ALMS computed every 1am and 1pm of each day of the month. ACTIVE_ALM_SUM resets to 0 at the beginning of each month. |
| ACTIVE_ALMS | Active alarm count (up to 250 alarms) |
| DD |
Parsed LOCALTIME by the SYSTEM-TIME block. |
| HH |
Parsed LOCALTIME by the SYSTEM-TIME block. |
| LOCALTIME | System time in seconds parsed by the SYSTEM-TIME block |
| MM |
Parsed LOCALTIME by the SYSTEM-TIME block. |
| MONTH_RPT_DONE | Flag to indicate if the average has already been computed for the month |
| SCHED_STAT_CURR | Flags to indicate if the scheduler (which updates ACTIVE_ALMS, SHELVED_ALMS, ACK_ALMS and STALE_ALMS) is still running. |
| SCHED_STAT_PREV | Flags to indicate if the scheduler (which updates ACTIVE_ALMS, SHELVED_ALMS, ACK_ALMS and STALE_ALMS) is still running. |
| SHELVED_ALM_AVG |
The calculated average of shelved alarms for last month which is computed in the CALC block. |
| SHELVED_ALM_SUM | Running total of SHELVED_ALMS computed every 1am and 1pm of each day of the month. SHELVED_ALM_SUM resets to 0 at the beginning of each month. |
| SHELVED_ALMS | Shelved alarms count |
| SHIFT_ADD_DONE | Flag to indicate if the sum has already been computed on 1am or 1pm. This is to make sure that the sum will only be computed once during 1am or 1pm. |
| SNAPSHOT_CNT | Number of times the sum for the four alarms types have been computed for the month. This will start at 0 at the beginning of each month and increments every time the sum is computed. |
| STALE_ALM_AVG |
The calculated average of stale alarms for last month which is computed in the CALC block. |
| STALE_ALM_SUM | Running total of STALE_ALMS computed every 1am and 1pm of each day of the month. STALE_ALM_SUM resets to 0 at the beginning of each month. |
| STALE_ALMS | Stale alarms count (active alarms for more than 24 hours) |
| STATION_NAME | Node where Operator Statistics Module is Assigned |
| YYYY |
Parsed LOCALTIME by the SYSTEM-TIME block. |
Open the module in Control Studio Off-Line mode to modify the module parameters and in Control Studio On-Line mode to view the current values of the module's parameters.