SPM module template theory of operation

SPM template alarm limits and management

There are 11 alarms provided by the module templates. All alarms are disabled by default except the PVBAD_ALM. The alarm limits and priorities can be modified, and alarms can be enabled or disabled individually in either the AI Block (RMT_SPM_HART) or the Alarm Block (RMT_SPM_FF). Default alarm limits, priorities, and enabled states are shown below.

Alarm Parameter Limit Value Enabled Priority
CV_HI CV/HI_ACT 1 False Advisory
CV_LO CV/LO_ACT 0 False Advisory
HI_ALM AI1/HI_ACT 95 False Warning
HI_HI_ALM AI1/HI_HI_ACT 100 False Critical
LO_ALM AI1/LO_ACT 5 False Warning
LO_LO_ALM AI1/LO_LO_ACT 0 False Critical
MEAN_HI MEAN/HI_ACT 95 False Log
MEAN_LO MEAN/LO_ACT 5 False Log
PVBAD_ALM AI1/BAD_ACTIVE --- True Critical
STDEV_HI STDEV/HI_ACT 1 False Advisory
STDEV_LO STDEV/LO_ACT 0 False Advisory

Typically alarms are left disabled and the SPM data is logged into the process historian for a period of time. Alarm limits are adjusted, and alarms are enabled, after operating experience determines the threshold of transition from normal to abnormal process conditions.