| Description | Limit |
|---|---|
|
For ProfessionalPLUS, Professional, Maintenance, Base Stations, and Operator Stations with Appropriate Licenses Installed |
|
|
Total unique runtime datalinks for systems using DeltaV Operate |
< 3000 per main picture (recommended) Important: Performance degradation could increase when 3000 datalinks are exceeded. |
|
Event Chronicle History Data Set |
100 MB recommended 4 GB maximum (Generally, 100 MB of disk space can hold between 250,000 and 500,000 records depending on the content of each event record.) |
|
Maximum open DeltaV Explorer applications |
1 |
|
Maximum open Control Studio applications |
4(1) |
|
Historical data values (DeltaV Continuous Historian) |
250(2) |
|
Open faceplates per module type |
4 |
|
Open detail displays |
1 |
|
Open pictures |
25 (recommended) |
|
Workstation Object Identifiers(3) |
32,000 |
|
For the ProfessionalPLUS workstation only |
|
|
Plant areas (including remote zone areas) |
250 |
|
Modules per unit |
255 |
|
Named sets |
835 (available) |
|
Alarm types |
235 (available) |
|
DeltaV user accounts per system |
200 (recommended) |
|
Maximum open engineering tasks on Professional Workstations |
60 (includes applications open on local ProfessionalPLUS workstations) |
|
Number of concurrent Professional Workstations connected |
10 |
|
For Application Stations only |
|
|
OPC data values |
30,000(1) |
|
Maximum assigned modules |
3,000 |
|
SCADA tags |
25,000 |
|
Historical data values |
DeltaV Continuous Historian: 30,250(2) Advanced Continuous Historian: 60,000 Embedded enterprise historian (OSIsoft PI Server): 30,000 Integrated enterprise historian (OSIsoft PI Server): 500,000 |
|
History samples/second rates |
DeltaV Continuous Historian: 3,000 Advanced Continuous Historian: 10,000 Enterprise historian (OSIsoft PI Server): 5,000 |
|
Workstation Object Identifiers (3) |
32,000 |