Using recommended engineering practices > Recommended practices for using fieldbus and Profibus

Write requests to static or non-volatile parameters

It is recommended that you limit the number of periodic writes to all static or non-volatile parameters such as HI_HI_LIM, LOW_CUT, SP, TRACK_IN_D, OUT, IO_OPTS, BIAS, STATUS_OPTS, SP_HI_LIM, and so on. Static parameter writes increment the static revision counter, ST_REV, and are written to the device's non-volatile memory. Fieldbus devices have a non-volatile memory write limit. If a static or non-volatile parameter is configured to be written periodically, the device can stop its normal operation after it reaches its limit or fail to accept new values. Consult the device documentation to determine if a parameter is static or non-volatile.

Another way to configure your system to avoid burning out non-volatile memory is to link a CALC block or PID block running in the controller to the AO block running in the device. This method avoids the use of asynchronous writes by writing to the AO block through a publisher/subscriber mechanism.